CDD 5.0: user manual – Rev.01
Page 28/63
4.6.2
Diagnostic operations by Handset
The external handset permits to perform a deep diagnostic of the door controller:
-
Check of ALL the settings
-
Speed profiles check
-
Drive readings check
-
Check of ALL I/O
4.6.2.1
I/O diagnostic
Access to “Main Menu ”
“Maintenance”
“MLC Monitor” and check the status of ALL inputs and
outputs of the door drive. When the signal is active, the correspondent signal description results
highlighted.
ATTENTION: in this menu the controller returns in Normal mode, and executes all the commands
coming from the Main Lift Controller.
The following table shows the I/O visualization:
INPUTS
OUTPUTS
DOC
EOC
DOS
DCC
DTBC
DCS
RSC
AUXC
RVS
RVC
DETC
AUXS
FFC
BUZS
- Table 20: I/O signals reported -
4.6.2.2
Profiles and measurements checks
Access to: “Main Menu”
“Maintenance”
“Monitor”. The “Monitor” menu permits to check the speed
profiles (speed reported in m/s), output power (in W) and output force (in N). By pressing OK button, it is
possible to access to the measurements table as reported below:
MEASUREMENTS
Column 1
Column 2
Symbol
Units
Symbol
Units
O
ms
Last panels opening time (even if
partial reopening)
D
mm
Learned door space (including clutch
movement)
C
ms
Last panels closing time (even if
partial reopening)
S
mm
Actual door position
E
imp
Encoder pulses (speed transducer)
counter status
T
°C
Estimated motor temperature
I
mA
Instantaneous motor current
F
N
Actual Closing force limit
B
%
% of battery charge (0=battery not
connected)
G
-
-
- Table 21: measurements reported in the monitor menu table -
NOTE: the space measurements are calculated based on the encoder mounted on the motor. The absolute
precision is then influenced by all the transmission system tolerances.