background image

 

 
 

Test Personnel 

 
Personnel require special training to conduct the dielectric withstand test.  They should understand 

electrical fundamentals clearly, and be aware that high voltage is adept and creative at completing a path to 
ground.    Instructions  should  include  a  warning  against  any  metal  jewelry.    Operators  should  not  allow 
others in the testing area, especially when tests are being conducted.  Organization is to be stressed.  The 
operator should keep the area free of unused leads and equipment. 

 

Testing Area 

 

The  area  used  for  conducting  the  dielectric  withstand  test  should  be  as  remote  as  possible  from 

normal  production  line  activities.    Only  personnel  actually  conducting  the  test  should  be  allowed  in  the 
area, and it should be taped or roped off to preclude casual entry by other employees.  In addition, the area 
should  be  marked  "WARNING  -  HIGH  VOLTAGE  TESTING"  or  the  equivalent  to  warn  others  of  the 
nature of the testing taking place. 

 
The  bench  being  used  should  be  non-conductive,  and  any  exposed  metal  parts  should  be  tied 

together and grounded.  If a conductive surface must be used, it should be grounded. 

 
Because  of  sparking  during  a  dielectric  test  failure,  it  is  not  safe  to  conduct  dielectric  withstand 

tests in combustible atmospheres. 

 
It  is  imperative  that  a  good  ground  be  provided  to  the  HT-S  unit.    Before  connecting  the  HT-S, 

ensure  that  a  low-resistance  ground  is  provided  by  the  building  wiring.    If  the  HT-S  is  used  on  a  high-
resistance  grounding  circuit,  dangerous  high  voltages  may  be  present  to  the  operator.    In  addition,  the 
power to the Testing Area should be provided with an easily reached shutoff switch which can be actuated 
by personnel outside the area if needed. 

 

 

 

Safety Techniques 

 

The high voltage circuit of the HT-S can be shut off at any time by pressing the 

RESET

 button.  

The  HT-S  has  been  provided  with  a  Reset  button  to  provide  an  unarmed  "Standby"  setting  when  it  is 
energized,  but  idle.    When  the  red 

RESET

  light  is  lit  the  tester  will  not  provide  high  voltage  until  the 

RESET

  button  and  the 

TEST

  button  have  been  pressed  in  order.    To  prevent  inadvertent  operation,  the 

operator should be instructed not to press the 

RESET

 button until the test is finish. 

 
The  HT-S  is  equipped  with  a  ground  continuity  check  which  will  not  allow  high  voltage  to  be 

applied if the Test Return Lead is not properly connected.  This is an important safety feature and should 
not be defeated unless two wire products are being tested.  In that event, it is imperative that the operator 
make absolutely sure the Test Return Lead is properly connected to the equipment being tested.  If the lead 
is  not  properly  connected,  a  dielectric  withstand  test  failure  may  energize  exposed  dead  metal  of  the 
equipment being tested.  Additionally, the HT-S may not recognize the failure.  The test will continue for 
its normal length of time, and the HT-S may show a "PASS", see connections for more details. 

 

Summary of Contents for HT-2000S

Page 1: ...HT S Series Dielectric Withstand Tester With Ground Continuity Check Instruction Manual for Models HT 2000S 0 2000VAC HT 2800S 0 2800VDC HT 3000S 0 2000VAC 0 2800VDC HT 4200S 0 3000VAC 0 4200VDC...

Page 2: ...2...

Page 3: ...g logic controlled circuit design and ergonomic front panel and represents the latest in high voltage production line testing To fully appreciate all the features of your new meter we suggest that you...

Page 4: ...Interface PN 00 RI 19 Interlock PN 00 XI 19 Section 3 20 Operating Instructions 20 Setting up your Tester 20 AC Line Voltage Requirements 20 Fuse Replacement 21 Initial Checkout Procedure 21 High Volt...

Page 5: ...5 Technical Assistance 30 Contact Information 30 Section 5 31 Maintenance and Calibration 31 Service Information 31 Cleaning 31 Calibration Information 31...

Page 6: ...ring the test due to low insulation resistance of the insulating material which separates the two conductors and 2 an abrupt dielectric breakdown due to electrical arcing or discharge either through t...

Page 7: ...that a low resistance ground is provided by the building wiring If the HT S is used on a high resistance grounding circuit dangerous high voltages may be present to the operator In addition the power...

Page 8: ...with his right hand This will allow the greatest separation between the operator and the test being conducted The HT S is designed to bleed the high voltage away after the test has concluded In order...

Page 9: ...emoving the Test Return Lead clip from the equipment under test and reconnecting it taking care to make a good connection The unit should then be retested If a failing result is repeated the connectio...

Page 10: ...leakage current is below the limit set by the rear panel adjustment Sporadic Leakage Current Failures If the red Excess Leakage LED light is on the buzzer sounds and the test is terminated the leakage...

Page 11: ...n a problem has been found with the insulation between primary and ground The equipment under test should be examined reworked and successfully tested before being shipped High Voltage Discharge The H...

Page 12: ...buzzer sounds and any voltage stored in the equipment being tested is bled off by a resistor bank in the HT S unit The voltage discharge progress is shown by the front panel meter Failure modes are s...

Page 13: ...ge Limit Voltage Adjust Ground Continuity Defeat Switch Ground Continuity Limit Ground Continuity Offset Tamper proof operation available by removing adjustment shafts ENVIRONMENTAL Operating Temperat...

Page 14: ...utes to become familiar with the use of its controls indicators and connectors The front panel features of the HT S are shown in Figure 1 and Figure 2 then described in Table 2 Figure 1 Front Panel Co...

Page 15: ...15 Figure 2 Front Panel Controls Indicators and Connectors for HT 4200S...

Page 16: ...ground circuit resistance is acceptable the green continuity LED will light and the test will continue If the Ground Check switch is defeated by the operator both LED s will be lit for the duration of...

Page 17: ...T S tester take a few minutes to become familiar with the use of its controls indicators and connectors The rear panel features of the HT S are shown in Figure 3 and described in Table 3 Figure 3 Rear...

Page 18: ...passed for testing of double insulated equipment and other types of equipment without a grounding pin in the line cord 9 Ground Resistance Setting Adjustment Used to adjust the Ground Continuity pass...

Page 19: ...Output Full Voltage 7 Output Excess Leakage 8 Output Hipot Pass 9 Output Hipot Fail 10 Output Any Failure 11 Output COM2 12 Common Table 4 Relay Interface Pin Configuration Interlock PN 00 XI The Saf...

Page 20: ...essories which meet the manufacturer s specifications shall be used Connect this equipment to grounded outlet only The integrity of the test system grounding is dependent on building ground If reshipm...

Page 21: ...s AC and 2800 Volts DC or up to 3000 Volts AC and 4200 Volts DC for HT 4200S generated by the HT S is exposed during this test A risk of shock exists Exercise care when using the HT S High Voltage Per...

Page 22: ...e High Voltage Device socket may be as much as 2000 volts AC or 2800 volts DC or up to 3000 Volts AC and 4200 Volts DC for HT 4200S Proceed with caution 1 Disconnect all leads of the HT S front panel...

Page 23: ...200S HT 3000S HT 2000S Voltage Type AC Leakage Current Level 5 mA High Voltage Ramp Time 1 second High Voltage Level 1200 Volts High Voltage Test Time 2 seconds Ground Continuity Level 1 50 HT 2800S V...

Page 24: ...of supply and turn the power switch to the I or ON position Push the RESET button The yellow TEST indicator should light indicating that the HT S is ready to test e Use the AC DC button to select the...

Page 25: ...reached The test can be terminated at any time by pressing the RESET button 6 Check the position of the Ground Check switch before testing Setting the Ground Check Switch This switch controls whether...

Page 26: ...t in shortcut circuit the green alligator clip end to the Ground Connector Tip connected on step 3 See Figure 6 5 For HT 4200S plug the supplied 18 AWG GL Test Lead Alligator Clip Banana Plug ends bla...

Page 27: ...sistance measurement is more than 1 50 the display will show OPEn Operation Techniques The following paragraphs describe how to operate the HT S tester Before proceeding with testing the HT S tester s...

Page 28: ...t set on the HT S unit the green Ground OK LED will light and the test will continue 5 2 Ramp the voltage at the rate set by the Ramp Time procedure o If leakage current between the AC pins of the pow...

Page 29: ...y cord and the chassis ground of the unit rises above the value set by the Leakage Limit procedure the red Excess Leakage LED will light the buzzer will sound and the test will terminate o If the leak...

Page 30: ...m Compliance West USA is available Phone 800 748 6224 Hours 8 30 AM 4 30 PM Pacific Time Also available on our web site at www compwest com Contact Compliance West USA 650 Gateway Center Way Suite D S...

Page 31: ...tion and or repair of instruments that are beyond their warranty period Contact the manufacturer for a cost quotation Ship the instrument and your remittance according to the instructions given by the...

Reviews: