IEC101/104 Gateway Configuration
The IEC101/104 gateway can be configured through the systems CLI or as part of a IEC104
network-wide service-group in the iSIM service management tool.
In any case the configuration should include the following parameters:
»
Application IP address – The application module must be configured with an IP address and
should be associated with a VLAN for the uplink traffic. This application IP interface acts as the
IEC104 server in the Ethernet network and represents all the IEC101 devices connected locally
to the router towards the IEC104 clients.
»
Optional remote IP addresses - When configuring the IEC104 service-group you should also
provide the IP addresses of the IEC104 clients so the proper service-aware firewall rules can be
defined.
»
IEC101 device parameters - For the serial interfaces the physical link properties should be
configured (baud-rate ,parity , stop bits). Furthermore the IEC101 addressing information
should be provided and and the devices should be assigned to the IEC104/101 gateway.
Figure 8 : Gateway service configuration in iSIM