background image

IE-SNC-P86xx-01 

 

 

 16  

Modbus  device  registers.  Address  could  be  by  1  higher,  depending  on  type  used 
communication library: 

Address [DEC] Address [HEX]  Value 

Type 

R/W 

40000 

0x9C40 

channel 1 temperature 

Int*10 

40001 

0x9C41 

channel 1 alarm status 

Ascii 

40002 

0x9C42 

channel 1 upper limit 

Int*10 

R/W 

40003 

0x9C43 

channel 1 lower limit 

Int*10 

R/W 

40004 

0x9C44 

channel 1 hysteresis 

Int*10 

R/W 

40005 

0x9C45 

channel 1 delay 

uInt 

R/W 

40006 

0x9C46 

channel 2 temperature 

Int*10 

40007 

0x9C47 

channel 2 alarm status 

Ascii 

40008 

0x9C48 

channel 2 upper limit 

Int*10 

R/W 

40009 

0x9C49 

channel 2 lower limit 

Int*10 

R/W 

40010 

0x9C4A 

channel 2 hysteresis 

Int*10 

R/W 

40011 

0x9C4B 

channel 2 delay 

uInt 

R/W 

40012 

0x9C4C 

channel 3 temperature 

Int*10 

40013 

0x9C4D 

channel 3 alarm status 

Ascii 

40014 

0x9C4E 

channel 3 upper limit 

Int*10 

R/W 

40015 

0x9C4F 

channel 3 lower limit 

Int*10 

R/W 

40016 

0x9C50 

channel 3 hysteresis 

Int*10 

R/W 

40017 

0x9C51 

channel 3 delay 

uInt 

R/W 

Description: 

 

read only register 

 

register is designed for write 

Int*10   

registry is in format integer*10 – 16 bits 

uInt   

registry range is 0-65535 

Ascii   

character 

Possible alarm states: 

no 

 

no alarm 

lo 

 

value is lower than set limit 

hi 

 

value is higher than set limit 

SOAP 

The  device  allows  you  to  send  currently  measured  values  via 

SOAP  v1.1

  protocol.  The 

device sends values in XML format to the web server. The advantage of this protocol is 

that  communication  is  initialized  by  the  device  side.  Due  to  it  is  not  necessary  use  port 
forwarding. Sending interval can be set in range 10-65535s using TSensor software. If the 

SOAP message can not be delivered, warning message via SNMP Trap or Syslog protocol 
is  sent.  The  file  with  the  XSD  schema  can  be  downloaded  from: 

www.cometsystem.cz/schemas/soapP85xx_v2.xsd

.  

SOAP  protocol  uses  monitoring  software  DBS  Sensor  monitor.  This  software  can  be 

purchased as optional accessories. 

Summary of Contents for P8610

Page 1: ...COMET SYSTEM www cometsystem cz P8610 intelligent thermometer with PoE P8631 intelligent 3 channel transducer with PoE USER MANUAL...

Page 2: ...es constant development and improvement of their products Manufacturer reserves the right to make technical changes to the device without previous notice Misprints reserved Manufacturer is not respons...

Page 3: ...P 16 Syslog 17 SNTP 17 Troubleshooting 18 I forgot the device IP address 18 I can not connect to the device 18 Error1 is displayed instead the measured value 19 Error2 is displayed in all channels ins...

Page 4: ...ollow instructions in this manual The device can be services only by a qualified person The device contains no serviceable parts inside standard means Don t use the device if it doesn t work correctly...

Page 5: ...mail addresses SMTP authentication is not supported in current firmware version Sending SNMP traps up to 3 configurable IP addresses Displaying the alarm status on web page Sending messages to Syslog...

Page 6: ...your network for P8631 Transducer up to 3 temperatures probes type DSTR162 C Mounting the device check if the equipments from previous chapter are available install the latest version of TSensor softw...

Page 7: ...connect the Ethernet connector if the power over Ethernet PoE is not used connect the power adapter 5V 250mA LEDs on LAN connector should blink after connecting the power P8610 Thermometer connection...

Page 8: ...show then click Help My device wasn t found Then follow the instructions MAC address is on product label The device is factory set to IP 192 168 1 213 gateway may not be entered if you want to use the...

Page 9: ...gs are saved after click on button Save changes Checking functions The last step is to check measured values on the device website In the address bar of the web browser enter the device IP address If...

Page 10: ...point 2 the temperature dropped below the limit value before the time delay expired alarm was not set In Point 3 the temperature has risen over limit again During the time delay the value does not dro...

Page 11: ...is not possible to change device configuration without entering the password Under SMTP you can set three IP addresses where will be send SNMP Traps There is also possible to enter a password for rea...

Page 12: ...any item in Telnet interface is not confirmed more than 5 minutes Telnet automatically ends and the device will be restarted Previous changes would not saved To save values is necessary to confirm the...

Page 13: ...ting private Sending SNMP Trap yes Website refresh interval s 60 Website enabled yes Modbus TCP protocol port 502 Modbus TCP enabled yes History storage interval s 60 SOAP server IP address 0 0 0 0 SO...

Page 14: ...lue line If all values are over upper lower limit the alarm line will be in the bottom top graph part displayed Values from history can be exported in CSV format History storage interval can be set us...

Page 15: ...n be sent to selected IP addresses Addresses can be set using TSensor software Traps are sent via UDP protocol on port 162 The device can send following traps Trap Description 0 0 Reset of the device...

Page 16: ...channel 3 lower limit Int 10 R W 40016 0x9C50 channel 3 hysteresis Int 10 R W 40017 0x9C51 channel 3 delay uInt R W Description R read only register W register is designed for write Int 10 registry is...

Page 17: ...tion error NTP synchronization error 00004 Settings changed Change settings via Modbus 00004 Hostname error Error sending SOAP messages 00006 Clearing channel 1 alarm Alarm determination 00006 Clearin...

Page 18: ...window Find device in TSensor software and press Change IP address Follow the software instructions To assign IP address automatically using DHCP server set the device IP address to 0 0 0 0 Device IP...

Page 19: ...TSensor software Error2 is displayed in all channels instead the measured value Error2 indicates short circuit of measurement bus Check if correct probes are connected Probes Pt100 Pt1000 Ni100 Ni100...

Page 20: ...IE SNC P86xx 01 20 Technical specifications Informations about technical specifications of the device Dimensions P8610 Thermometer P8631 Transducer Chapter 6...

Page 21: ...racy P8631 depending on used probe e g probe DSTR162 C parameters 0 5 C in temperature range from 10 C to 80 C 2 0 C in temperature range from 10 C td 40 C Resolution 0 1 C P8610 temperature measureme...

Page 22: ...s product may cause radio interference in which case the user may be required to take adequate measures to correct this interference EMC resistance SN EN 61326 1 2006 cor 1 2007 Electrical safety SN E...

Page 23: ...ces must be professionally destroyed in accordance with EU Directive 2002 96 ES of 27th January 2003 Technical support and service Technical support and service is provided by distributor Contact is i...

Page 24: ...d watertight IP67 sensor connected to PVC cable with lengths 1 2 5 or 10m Power supply Adapter A1825 Power supply adapter with CEE 7 plug 100 240V 50 60Hz 5V DC 1 2A for P8610 Thermometer or P8631 Tra...

Page 25: ...oftware DBS Sensor Monitor for online data collection and data analysis from Ethernet sensors It contains all components for data acquisition from sensors including a one license DBV Database Viewer F...

Page 26: ...IE SNC P86xx 01 26...

Page 27: ...IE SNC P86xx 01 27...

Page 28: ...www cometsystem cz...

Reviews: