IE-SNC-P86xx-01
17
Syslog
The device allows sending text message to selected Syslog server. Events are send using
UDP
protocol on
port 514
. Events when Syslog messages are send:
Text
Event
<00001> Device restart
Device reboot
<00001> SOAP connection error
Error sending SOAP messages
<00002> Alarm channel 1 temp high/low
Alarm activation
<00002> Alarm channel 2 temp high/low
<00002> Alarm channel 3 temp high/low
<00003> NTP connection error
NTP synchronization error
<00004> Settings changed
Change settings via Modbus
<00004> Hostname error
Error sending SOAP messages
<00006> Clearing channel 1 alarm
Alarm determination
<00006> Clearing channel 2 alarm
<00006> Clearing channel 3 alarm
<00006> Testing message
Test Syslog message
SNTP
The device allows time synchronization with NTP (SNTP) server. Time synchronization is
made every 8 hours. SNTP IP address can be set using TSensor software. It is also possible
set GMT offset for correct time zone. Time is used in history tables and history CSV files.
Maximum jitter between two time synchronizations can be 30s.