IE-SNC-P86xx-01
13
Factory configuration
Using TSensor software –
Factory configuration
button, the device can be set to factory
configuration. Network parameters (IP address, Subnet mask, Gateway) are left without
changes. Factory parameters settings:
Parameter
Value
IP address of SMTP server
0.0.0.0
E-mail recipients addresses
cleared
E-mail sender
sensor@IP
E-mail sending enabled
no
IP addresses SNMP traps recipients
0.0.0.0
Password for SNMP reading
public
Password for SNMP writing
private
Sending SNMP Trap
yes
Website refresh interval [s]
60
Website enabled
yes
Modbus TCP protocol port
502
Modbus TCP enabled
yes
History storage interval [s]
60
SOAP server IP address
0.0.0.0
SOAP source port
0
SOAP destination port
80
SOAP service target site
cleared
SOAP protocol enabled
no
Syslog server IP address
0.0.0.0
Syslog protocol enabled
no
SNTP server IP address
0.0.0.0
GMT offset [min]
0
SNTP synchronization enabled
no
MTU
1400
Turn on all channels
yes
Upper limit [°C]
125
Lower limit [°C]
-55
Hysteresis – hysteresis for alarm clearing [°C]
1
Delay – time-delay of alarm activation [s]
30
Password to access the settings
cleared
Device name
P8610 sensor or P8631 sensor