Option 1 - use MainsPro relay 

 
For any application shown above on the 

Pict. 1

, or 

Pict. 2

, or 

Pict. 3

 the concept of 2 independent units can 

be used. 
 
MainsPro sw version 1.4.1, hw version: 1.2 is independent ComAp protection relay which measures network 
voltage and frequency and trips the supervised CB in case network values are not within adjusted limits. 
 
In this concept, 2 independent units are used - controller and MainsPro unit. The primary breaker is 
controlled directly from the controller; the secondary breaker (redundant) is controlled from the controller 
through MainsPro unit.  
 
Once controller detects network parameters out of limits, it trips the primary circuit breaker and 
simultaneously gives a command to the MainsPro unit to trip the secondary circuit breaker. 
 
Once the MainsPro relay detects network parameters out of limits, it trips the secondary circuit breaker and 
simultaneously gives a signal to controller to trip the primary circuit breaker. 
 
This interconnection ensures, that both breakers are tripped in every case the network parameters are out of 
limits and also both the controller and MainsPro relay are tested every case the network parameters are out 
of limits. In case any of the units fail, the alarm: GCB fail or MGCB fail occurs (In case MainsPro relay fail, 
controller will detect redundant CB fail due to non receiving change on the redundant CB feedback. In case 
controller fails to open the primary CB, it will detect the primary CB fail due to non receiving change on the 
primary CB feedback signal) 
 

Wiring instructions of this concept: 
 

·

  Signals for control of primary CB has to be configured to any physical binary outputs 1 – 8 of the 

controller. 

·

  Signals for control of redundant CB has to be configured to any physical binary output 9-16 (9-12 

based on the controller hardware) of the controller and connected to Tripping input of the MainsPro 
unit – BI1 Ext Trip. 

 

·

  Signals for both primary and secondary CB feedback has to be configured to any binary input of the 

controller. 

·

  Signal from MainsPro relay, signalizing that the CB shall be tripped has to be connected to the 

Controller, LBI: Ext MP Trip. 

·

  All these signals are already prepared in default archives and there is no need to configure anything 

in relation to this interconnection. 

 
 
Controller and MainsPro relay have to be connected as follows: 
 
 

Summary of Contents for IG-NT-BB

Page 1: ...ied to input terminal In case the logic on particular installation site is opposite e g binary outputs are high side switch type the corresponding change has to be taken into account in the scheme as...

Page 2: ...undant GCBs and 1 MCB The breaker redundancy requirement of the VDE AR N 4105 is created with the GCB breakers to ensure the gen set is disconnected from network and any remaining customer system as 4...

Page 3: ...gnal to controller to trip the primary circuit breaker This interconnection ensures that both breakers are tripped in every case the network parameters are out of limits and also both the controller a...

Page 4: ...blic ISO 9001 Certified C omAp s r o Q u ality Managem e n t Tel 420 246012111 Fax 420 2 66316647 E mail info comap cz Internet http www comap cz Pict 4 Block scheme how to connect the Controller and...

Page 5: ...6647 E mail info comap cz Internet http www comap cz Pict 5 Block scheme how to connect the Controller and MainsPro unit in case circuit breaker is used for GCB control in SPI or SPtM application For...

Page 6: ...ation in case of any failure Circuit breaker has to be design for compliance with VDE AR N 4105 Example could be e g Schneider Electric NSX NS and NW family or ABB Tmax or Emax family plus many others...

Page 7: ...MainsPro Controller Groupe Name of setpoint Value Mains protect Mains V MP 80 Mains V MP 115 Mains f 51 5Hz Mains f 47 5Hz Mains Avg V MP 110 MainsProtDel 0s Protect type LOW VOLT Sync Load ctrl Main...

Reviews: