Pict. 5 . Block scheme how to connect the Controller and MainsPro unit, in case circuit breaker is used for 
GCB control – in SPI or SPtM application. For MGCB application the scheme is identical but instead of GCB 
the MGCB signals are used. 

 
 
This means, that both units serve as independent units and so each of them measures independently the 
Mains parameters and in case the out of range is detected, both CB are tripped. 
 
 
 
 
 
 

Summary of Contents for IG-NT-BB

Page 1: ...ied to input terminal In case the logic on particular installation site is opposite e g binary outputs are high side switch type the corresponding change has to be taken into account in the scheme as...

Page 2: ...undant GCBs and 1 MCB The breaker redundancy requirement of the VDE AR N 4105 is created with the GCB breakers to ensure the gen set is disconnected from network and any remaining customer system as 4...

Page 3: ...gnal to controller to trip the primary circuit breaker This interconnection ensures that both breakers are tripped in every case the network parameters are out of limits and also both the controller a...

Page 4: ...blic ISO 9001 Certified C omAp s r o Q u ality Managem e n t Tel 420 246012111 Fax 420 2 66316647 E mail info comap cz Internet http www comap cz Pict 4 Block scheme how to connect the Controller and...

Page 5: ...6647 E mail info comap cz Internet http www comap cz Pict 5 Block scheme how to connect the Controller and MainsPro unit in case circuit breaker is used for GCB control in SPI or SPtM application For...

Page 6: ...ation in case of any failure Circuit breaker has to be design for compliance with VDE AR N 4105 Example could be e g Schneider Electric NSX NS and NW family or ABB Tmax or Emax family plus many others...

Page 7: ...MainsPro Controller Groupe Name of setpoint Value Mains protect Mains V MP 80 Mains V MP 115 Mains f 51 5Hz Mains f 47 5Hz Mains Avg V MP 110 MainsProtDel 0s Protect type LOW VOLT Sync Load ctrl Main...

Reviews: