Mandatory settings of network protections in controller and MainsPro 

The following tables determine the network protections parameters, which have to adjusted in the controller 
and in MainsPro (in case MainsPro is used). After parameters adjustment the change of parameters has to 
be disabled – either by password in case of controller or mechanical seal in case of MainsPro. 
 
Controller 

Groupe 

Name of setpoint 

Value 

Mains protect 

Mains <V MP 

80% 

  

Mains >V MP 

115% 

 

Mains >f 

51.5Hz 

  

Mains <f 

47.5Hz 

  

Mains Avg>V MP 

110% 

  

MainsProtDel 

0s 

  

Protect type 

LOW VOLT 

 Sync/Load ctrl 

MainsSyncVMax 

110% 

  

MainsSyncVMin 

85% 

  

MainsSyncFmax 

50,05Hz 

 

MainsSyncFmin 

47.50Hz 

  

MainsSyncTShrt 

5s 

  

MainsSyncTLong 

60s 

  

Slow Load ramp 

600s 

 

MainsPro 
 

Groupe 

Name of  
setpoint 

Value 

Note 

U<> 

U> 

115% 

Value has to be set in absolute value. So 
have to be calculated from NominalVoltage 
and percentage at Value column  

  

U>Del 

0.00s 

 

 

U< 

80% 

Value has to be set in absolute value. So 
have to be calculated from NominalVoltage 
and percentage at Value column  

 

Avg U> 

110% 

Value has to be set in absolute value. So 
have to be calculated from NominalVoltage 
and percentage at Value column 

 F<> 

f> 

51.50Hz 

 

  

f>Del 

0.00s 

 

  

f< 

47.50Hz 

 

  

f<Del 

0.00s 

 

 f(BI) 

f(BI1) 

Ext 

 

 f(RE) 

f(RE1) 

!CommTrpPer   

  

f(RE2) 

!Internfail 

 

 

f(RE3) 

U Sig 

 

 

f(RE4) 

F Sig 

 

 

Summary of Contents for IG-NT-BB

Page 1: ...ied to input terminal In case the logic on particular installation site is opposite e g binary outputs are high side switch type the corresponding change has to be taken into account in the scheme as...

Page 2: ...undant GCBs and 1 MCB The breaker redundancy requirement of the VDE AR N 4105 is created with the GCB breakers to ensure the gen set is disconnected from network and any remaining customer system as 4...

Page 3: ...gnal to controller to trip the primary circuit breaker This interconnection ensures that both breakers are tripped in every case the network parameters are out of limits and also both the controller a...

Page 4: ...blic ISO 9001 Certified C omAp s r o Q u ality Managem e n t Tel 420 246012111 Fax 420 2 66316647 E mail info comap cz Internet http www comap cz Pict 4 Block scheme how to connect the Controller and...

Page 5: ...6647 E mail info comap cz Internet http www comap cz Pict 5 Block scheme how to connect the Controller and MainsPro unit in case circuit breaker is used for GCB control in SPI or SPtM application For...

Page 6: ...ation in case of any failure Circuit breaker has to be design for compliance with VDE AR N 4105 Example could be e g Schneider Electric NSX NS and NW family or ABB Tmax or Emax family plus many others...

Page 7: ...MainsPro Controller Groupe Name of setpoint Value Mains protect Mains V MP 80 Mains V MP 115 Mains f 51 5Hz Mains f 47 5Hz Mains Avg V MP 110 MainsProtDel 0s Protect type LOW VOLT Sync Load ctrl Main...

Reviews: