Mandatory settings of network protections in controller and MainsPro
The following tables determine the network protections parameters, which have to adjusted in the controller
and in MainsPro (in case MainsPro is used). After parameters adjustment the change of parameters has to
be disabled – either by password in case of controller or mechanical seal in case of MainsPro.
Controller
Groupe
Name of setpoint
Value
Mains protect
Mains <V MP
80%
Mains >V MP
115%
Mains >f
51.5Hz
Mains <f
47.5Hz
Mains Avg>V MP
110%
MainsProtDel
0s
Protect type
LOW VOLT
Sync/Load ctrl
MainsSyncVMax
110%
MainsSyncVMin
85%
MainsSyncFmax
50,05Hz
MainsSyncFmin
47.50Hz
MainsSyncTShrt
5s
MainsSyncTLong
60s
Slow Load ramp
600s
MainsPro
Groupe
Name of
setpoint
Value
Note
U<>
U>
115%
Value has to be set in absolute value. So
have to be calculated from NominalVoltage
and percentage at Value column
U>Del
0.00s
U<
80%
Value has to be set in absolute value. So
have to be calculated from NominalVoltage
and percentage at Value column
Avg U>
110%
Value has to be set in absolute value. So
have to be calculated from NominalVoltage
and percentage at Value column
F<>
f>
51.50Hz
f>Del
0.00s
f<
47.50Hz
f<Del
0.00s
f(BI)
f(BI1)
Ext
f(RE)
f(RE1)
!CommTrpPer
f(RE2)
!Internfail
f(RE3)
U Sig
f(RE4)
F Sig