IGS-NT Safety Manual 1.0 rev.8 

Page 1 of 7 

 

IGS-NT-1.0 – Safety Manual / ©ComAp – March 2014 / IGS-NT-1.0-SafetyManual rev.8.pdf 

 

 

 

 

ComAp, a s. 
Kundratka 2359/17 
180 00 Praha 8 
Czech Republic

 

ISO 9001 Certified 

Co

mAp s.r.o.

Qu

ality Manageme

nt

 

Tel.: +420 246012111 

Fax: +420 2 66316647 

E-mail: [email protected]  

Internet: http://www.comap.cz 

 
 

IGS-NT Safety manual 

This document shall provide the detail description for customers of ComAp paralleling controllers, namely for 
IGS-NT line members (controllers named in the following bullets) how to connect the controller and coherent 
systems, to comply with VDE-AR-N-4105 requirements, namely with the requirement for Single fault 
tolerance. 
 
This manual is dedicated for following ComAp controllers: 

·

  IG-NT-BB 

·

  IG-NTC-BB 

·

  IS-NT-BB 

·

  IS-NTC-BB 

·

  IM-NT-BB 

·

  IM-NTC-BB 

·

  AIO-NT-BB 

·

  AIO-NTC-BB 

and all these controllers are generally named as a “controller” in this document. 

 
 

Hint: 

On all the schemes shown below, it is assumed, that: 

·

  All binary outputs are activated as low side switches, it means in active state the BO provides minus 

pole of the controller power supply. 

·

  All binary inputs are active when minus pole of the controller power supply is applied to input 

terminal. 

In case the logic on particular installation (site) is opposite (e.g. binary outputs are high side switch type) the 
corresponding change has to be taken into account in the scheme as well (interchange between L- and L+ 
terminals). Due to better readability of the schemes this change is not shown. 
 
In the text below there is referred about circuit breakers, CB. These CB are meant as the 2 redundant CB 
which the norm VDE-AR-N 4105 requires. Based on the target application – SPI, SPtM or MGCB the 
redundant breakers are either GCB1 and GCB2 in case of SPI and SPtM application, or MGCB1 and 
MGCB2 in case of MGCB application. Due to this variability the redundant breakers are referred as CB and 
based on the target application this means either GCB or MGCB. 

Single Fault Tolerance requirement 

 
VDE-AR-N 4105:2011-08 requests in point A.6 that central NS protection, integrated interface switch as well 
as the trigger circuit consisting of integrated NS protection and integrated interface switch shall meet the 
requirements for single-fault tolerance. 
 
This requirement can not be achieved with any single controller mentioned above therefore 2 independent 
devices (or units) have to be used instead of just one controller.  
 
There are following possibilities: 
 

1.  ComAp controller (mentioned above) plus MainsPro controller (independent mains protection unit).  

 

 

Summary of Contents for IG-NT-BB

Page 1: ...ied to input terminal In case the logic on particular installation site is opposite e g binary outputs are high side switch type the corresponding change has to be taken into account in the scheme as...

Page 2: ...undant GCBs and 1 MCB The breaker redundancy requirement of the VDE AR N 4105 is created with the GCB breakers to ensure the gen set is disconnected from network and any remaining customer system as 4...

Page 3: ...gnal to controller to trip the primary circuit breaker This interconnection ensures that both breakers are tripped in every case the network parameters are out of limits and also both the controller a...

Page 4: ...blic ISO 9001 Certified C omAp s r o Q u ality Managem e n t Tel 420 246012111 Fax 420 2 66316647 E mail info comap cz Internet http www comap cz Pict 4 Block scheme how to connect the Controller and...

Page 5: ...6647 E mail info comap cz Internet http www comap cz Pict 5 Block scheme how to connect the Controller and MainsPro unit in case circuit breaker is used for GCB control in SPI or SPtM application For...

Page 6: ...ation in case of any failure Circuit breaker has to be design for compliance with VDE AR N 4105 Example could be e g Schneider Electric NSX NS and NW family or ABB Tmax or Emax family plus many others...

Page 7: ...MainsPro Controller Groupe Name of setpoint Value Mains protect Mains V MP 80 Mains V MP 115 Mains f 51 5Hz Mains f 47 5Hz Mains Avg V MP 110 MainsProtDel 0s Protect type LOW VOLT Sync Load ctrl Main...