CAUTION
:
l
The shield ground connections of the RS-232 port, LAN port, PoE port, I/O port and Frame Ground terminal
are internally connected. The system grounding is designed to be at a zero ground potential; this zero
ground potential extends through the cable and to peripheral equipment (e.g. a vision system, PLC, etc.). To
ensure safe operating conditions, it is strongly recommended that all ground connections are checked to
ensure that a zero ground potential is met.
l
All general-purpose inputs share a common connection (IN COMMON). Therefore, all input devices must be
the same; either current sinking or current sourcing. Mixing inputs with sinking and sourcing could damage
the I/O module or your devices.
l
All general-purpose outputs share a common connection (OUT COMMON). Therefore, all output devices
must be the same; either current sinking or current sourcing. Mixing outputs with sinking and sourcing could
damage the I/O module or your devices.
l
When connecting the In-Sight 7000 series vision system to the CIO-MICRO or CIO-MICRO-CC I/O module,
the I/O module's , TRIGGER-, HS OUT 0, HS OUT 1 and HS COMMON terminals are not
supported. Do not connect wire leads from remote devices to these terminals.
l
When connecting the In-Sight 7000 series vision system to the CIO-MICRO or CIO-MICRO-CC I/O module,
the I/O module's I/O port (DB15) is not supported. Do not connect anything to this port.
l
Cable shielding can be degraded or cables can be damaged or wear out more quickly if a service loop or
bend radius is tighter than 10X the cable diameter. The bend radius must begin at least six inches from the
connector.
41
Wiring Inputs and Outputs