Getting Started with In-Sight 1010
8
Serial and digital signals are provided on the breakout cable (see Table 1-3). An optional
Breakout Module
is available to assist in the task of wiring these signals.
Table 1-3. Breakout Cable Wiring and Connector Pinouts
Pin
Signal
Breakout Cable
Wire Color
Breakout Module
Terminals
In-Sight 1010 Functionality
1
+24 VDC
White-Green
1,2,3,4,6,8,10
Power supply to the In-Sight 1010.
2 Trigger
+
Green
12
Trigger to start read.
0V/24V signal from the proximity
sensor or PLC.
3 Trigger
- White-Orange
13
0V common with the proximity
sensor or PLC.
4
Output 0
Blue
11
Pass/Fail status signal.
5 Output
1 White-Blue
9
Job Completed signal. On receipt
of this signal, read the Pass/Fail
status signal.
6
Serial Receive
Orange
5
No functionality.
7 Serial
Transmit White-Brown
7
The code read is transmitted via
this pin.
8
Ground
Brown
14,15,16
0V supply to the In-Sight 1010.
Digital Input
When the In-Sight 1010 is in ‘Trigger’ mode, a code read is started on receipt of a 24V signal,
typically from a proximity sensor or PLC.
Digital Outputs
The In-Sight 1010 can send a
Job Completed
output pulse of 20ms that activates when the
code has been read.
Also, the In-Sight 1010 can be configured to compare the code read to an expected string and
report a Pass/Fail signal based on the result of that match. On receipt of the
Job Completed
signal, read the Pass/Fail status signal.
Connecting to a PLC
Connect a 2k resistor between the output signal and 24V.
•
Pass - 0V.
•
Fail - 24V.
The active state of the Job Completed output pulse is 0V.