33
4.3
Connection of control panel
4.3.1 Electrical
feed
The electrical power supply of the control panel is done by Figure 5 terminal A with a
voltage of 110 ~ 230V ± 10% 50 - 60 Hz. The connection must be made by 3 wires with a
minimum diameter of 1.5 mm, being mandatory the connection of the ground wire to the
supply terminal A. The wire line passes through a fuse. The maximum power
consumption for a control panel is 70 W. The connection will be made according to the
label on the bottom of the chest.
Figure 6: Power supply label
DISCONNECT the mains voltage and batteries before
working inside the control panel
Do not cut the power supply during the boot process.
Such action may cause control panel malfunction
4.3.2 Output
card
Figure 7: Output card layout
The output card has the following outputs:
1. Battery.
For DVB models, this terminal is connected with the batteries. It is only active on the card C1
(See Figure 5).
Through this connection the battery is charged and monitored. The battery charge is
compensated depending on the battery temperature. This input / output is protected by a
1
2
3
Zone 1 or 3
Zone 2 or 4
4
5
6
4
5
6
Sounder connection using the alarm relay and
the 30 Vdc auxiliary outputs