Digital fire detection control panel
LYON
FIRE PROTECTION MANUFACTURER
Ctra. de Molins de Rei a Rubí, Km. 8,4 - 08191 RUBÍ (Barcelona) ESPAÑA.
56
Tlf.: +34 935 862 690 - Fax:+34 936 999 261 - [email protected] -
www.cofem.com
SEARCH FOR LOOP POINTS: It detects elements in the installation and it shows a
list the same as the one above.
ASSIGN NUMBER TO POINT: To save the programming number of each point in
the control panel. The programming number is the identification number that each
elements has (from 1 to 65533
and the same number may never be repeated in a
loop
). The control panel must know this programming number to identify the
elements.
AUTOMATIC LOOP SETUP: Find the points of the loop and assigns a setup number
to each point in order of programming numbers starting with the smallest.
DELETE POINT: To delete a point that is no longer connected to the loop and is still
configured, delete the programming number and the label of the element.
REPLACE POINT: Replace one point in the loop by another. This is the appropriate
option to replace an element since it saves the label. Take into account that it is
necessary to first physically replace the element with the control panel disconnected,
then start up the control panel and lastly run this menu option
DELETE LOOP POINTS: To eliminate all the points configured in a loop both
programming numbers and labels.
3.2.3.3.2.- Configure logical relays.
Option 2 of the CONFIGURE menu. In this menu we have the option of configuring all the
parameters referred to logical relays connected to the loop, that is to say, the type of actuation, delay, etc.
Within the CONFIGURE LOGICAL RELAYS menu we have eight submenus:
RELAY ACTUATION: The relays can be configured as Sounders, Switches and relay.
SOUNDERS: these are activated automatically if they have been so configured and
this is affected by the silence sounders button.
MANOEUVRES: these are activated automatically if they have been so configured
and are not affected by the silence sounders button
Crossed Relay L: this is activated automatically when there is 2 devices in alarm
inside its activation List. It is not affected by the silence sounders button neither
evacuation button.
Crossed Relay SL: this is activated automatically when there is 2 devices in alarm
inside one of its activation Sub-List. It is not affected by the silence sounders button
neither evacuation button.
NOTE: There is a manual call point version PUCAYEXT. This device is computed
by control panel as the acivation of two devices. In this way, it allows triggering the
rossed Relay L and Crossed Relay SL only activating this device.
RELAY: this is activated automatically and neither the evacuation nor the silence
sounders keys affect it
.
DELAY: The time period within which the necessary alarms are generated in order for a
logical relay to be activated and the actuation of the same. A delay of between 0 and 9
minutes 59 seconds is possible.
DAY/ NIGHT: In this submenu we can configure the type of activation of a logical relay
(active with or without delay, inactive) for a daytime and night schedule. We will be able to
activate the day mode independently for every day of the week.
PHYSICAL SITUATION: Loop and point number where the logical relay is.
LABEL: To introduce a description of the relay for its identification in the installation.
ACTIVATION MODE: Within this menu we find two options: General Activation and
Activation by List.
GENERAL ACTIVATION: This option causes the relay to activate when an alarm
occurs in any element of the control panel.
ACTIVATION BY LIST: We can configure the activation lists of the relay selecting the
points that we want to activate the relay. When any one of the point defined in the list
goes into alarm status, the relay activates. The control panel enables up to 8 different