3.1. System Programming
By selecting option
4
System Configuration
, the access code for level 3 will be requested. Enter the code and
confirm with the
ENTER
key.
AN ACCESS CODE WILL BE REQUESTED
Nº
9000
The following menu will appear on the display:
1
Review history
2
Label elements
3
Configure
4
Update date and time
5
Day/Night times
6
Activate test/normal mode
7
Language menu
8
Communications
3.2. Configure
Select option
3
Configure,
and confirm with the
ENTER
key
.
The following menu with 6 options will appear on the display:
1
Loop Configuration
2
Configure Logical Relays
3
Configure Alarm Zones
4
Configure Element Sensitivity
5
Additional Passwords
6
Configure Auto Evacuation
3.3. Configure Loop
By selecting option
1
Loop Configuration
the option will be the first to appear. Confirm with the
ENTER
key. You will be asked for the number of the loop to be configured.
The following menu with 3 options will appear on the display:
1
Sensitivity of a type
2
Flashing
3
Point configuration
3.4. Loop Configuration
The first step is to configure the elements of the loop so that the control unit recognises all the Elements that
are connected to each of the loops.
By selecting option
3
Point Configuration
the option will be the first to appear. Confirm with the
ENTER
key.
The following menu with 7 options will appear on the display:
1
View loop information
2
Search for loop element
3
Assign a number to an element
4
Automatic loop configuration
5
Delete point
6
Delete programming number
7
Delete loop element
By selecting option
2
Search for loop element
the option will be the first to appear. Confirm with the
ENTER
key.
This function passes all the programming numbers to the control unit memory and, after a few seconds, the total
number of elements that have been configured in the loop will appear on the display and how many there are of
each type. This search will take approximately 80 seconds.
Check that the information displayed is correct.
Important note
:
This step must be performed for each of the installed loops. It must be done even if there are no elements connected
to the loop.