By selecting option
1
Configure Zone
the option will be the first to appear. Confirm with the
ENTER
key.
Important:
8 possible lists are available for each zone. Firstly, you will be asked for the loop and number of the
first point. Secondly, you will be asked for the last point number for the list. Always confirm with the ENTER key.
Once configuration of the zone is complete, it is important to view the zone configuration using option 5 in order to
check it has been configured correctly.
In order to give a name to a zone, you must select option
4 Label
, confirming with the
ENTER
key. Within this
option, select the character (letter or number) using the up and down arrow keys and change position in the label
using the left and right cursors arrow keys. Save the label using the
ENTER
key.
6. Replacing a loop element
1
The first step is to know exactly which element is to be replaced.
Number of the LOOP in which it is installed
Number of the point within the loop
PROGRAMMING number of the loop element
2
Make note of the loop configuration.
See chapter:
3.4 Loop Configuration.
It is option 1 on the element configuration menu.
3
Delete the point removed from the loop.
See chapter:
3.4 Loop Configuration.
It is option 5 of the element configuration menu.
4
Insert the new element (having previously made note of the programming number).
5
Search loop element. When this has been completed, the configuration will be shown on the display. Check that
the configuration is the same as in step 2 above, but with the new element added.
See chapter:
3.4 Loop Configuration.
It is option 2 of the point configuration menu.
6
Assign number to element.
See chapter:
3.5 Assign a number to a point.
It is option 3 of the point configuration menu.
7
Whenever a modification is made, the changes should always be checked.
See chapter:
Monitor.
It is option 1 of the main menu.
DISCONNECT the 110~230V POWER supply and the BATTERIES before
accessing the interior of the control unit.
NOTE:
COFEM S.A. reserves the right to make changes due to typographical errors, inaccuracies in the current information or program and/or equipment
improvements at any time and without prior notice.
L O O P : 0 1 A 3 0 X T A : 0 0 0 M D A x Y : 0 0 0
A 3 0 X H A / S : 0 0 4 S I R A Y : 0 0 0
P O I N T S : 0 0 5 A 3 0 X H T C O : 0 0 0 M S T A Y : 0 0 0
P U C A Y : 0 0 1 K M A Y : 0 0 0