When monitoring, the third line describes the type of element according to the following table:
TYPE OF ELEMENT
SCREEN DESCRIPTION
PUCAY
MANUAL CALL POINT
A30XHTCO MULTI-SENSOR
SIRAY / SIRAYL
ANALOGUE SIREN
A30XHA THERMAL
OPTICAL
SENSOR
A30XHA-S OPTICAL
SENSOR
MDA1Y
MASTER FOR ONE RELAY
MDA2Y DOUBLE
RELAY
MASTER
MSTAY TECHNICAL
SIGNALS
MASTER
KMAY ANALOGUE
MASTER
MYOA
MASTER RELAY AND TECHNICAL
SIGNALS
3.2.2.5.- Activate / Deactivate logical relays.
Option 2 of the main menu, LOGICAL RELAYS ACTIVATION. In this menu we have 5 submenus:
LIST TRIPPED RELAYS
,
ACTIVATE A SINGLE RELAY
,
DEACTIVATE A SINGLE RELAY
,
ACTIVATE ALL SIRENS
,
ACTIVATE ALL SWITCHES.
Exactly as they suggest, the submenus enable us to activate groups of relays configured as switches
and sounders or make individual activations. Also there is the option to deactivate relays individually.
3.2.2.6.- Activate / Deactivate general relays.
Option 3 of the main menu, GENERAL RELAYS ACTIVATION. In this menu we have 2
submenus: GENERAL SIREN RELAY
,
FAULT RELAY. Within each of these we have 5 options:
ACTIVATE RELAY
,
DEACTIVATE RELAY
,
CHANGE DELAY
,
DISABLE RELAY
and
ENABLE
RELAY.
Exactly as they suggest the submenus enable us to activate or deactivate the relay, to configure its
delay between 0 and 9 minutes 59 seconds, and disabling or enabling the relay.
3.2.2.7.- System configuration.
O
ption 4 of the main menu,
SYSTEM CONFIGURATION. From this option after entering the
password for level 3 access we are able to access the configuration menu.
See chapter
3.2.3.
3.2.2.8.- Enable/ Disable elements and zones.
Option 5 of the main menu, PUT ZONES INTO/OUT OF SERVICE. In this menu we have 5
submenus: PUT POINT INTO SERVICE
,
SET POINT OUT OF SERVICE
,
PUT ZONE INTO
SERVICE
,
SET ZONE OUT OF SERVICE and
LIST OUT OF SERVICE ZONES
Exactly as they suggest the submenus enable us to enable/disable zones or elements individually, and
to view a list of the out of service zones.
3.2.2.9.- System test.
Option 6 of the main menu, SYSTEM TEST. This is an option that allows us to perform a test of the
control panel indicators. In this test all LED should be illuminated, the buzzer should sound and the
following screen be shown:
█ █ █ █ █ █ █ █ █ █ █ █ █ █ █ █ █ █ █ █ █ █ █ █ █ █ █ █ █ █ █ █ █ █ █ █ █ █ █ █
█ █ █ █ █ █ █ █ █ █ █ █ █ █ █ █ █ █ █ █ █ █ █ █ █ █ █ █ █ █ █ █ █ █ █ █ █ █ █ █
█ █ █ █ █ █ █ █ █ █ █ █ █ █ █ █ █ █ █ █ █ █ █ █ █ █ █ █ █ █ █ █ █ █ █ █ █ █ █ █
█ █ █ █ █ █ █ █ █ █ █ █ █ █ █ █ █ █ █ █ █ █ █ █ █ █ █ █ █ █ █ █ █ █ █ █ █ █ █ █