Digital fire detection control panel
LYON
FIRE PROTECTION MANUFACTURER
Ctra. de Molins de Rei a Rubí, Km. 8,4 - 08191 RUBÍ (Barcelona) ESPAÑA.
Tlf.: +34 935 862 690 - Fax:+34 936 999 261 - [email protected] -
www.cofem.com
17
1.5.2.- Analogue alarm Manual Call Point (PUCAY)
The re-settable Analogue and Addressable manual call
point (with short-circuit isolator) incorporates an action indicator
(LED) which is illuminated in the case of being manually
activated (alarm).
The flashing of the transparent red LED indicates
communication with the Control panel Lyon system, and if it
remains on it indicates the alert status of the button.
There is a version “PUCAYEXT” that it is computed by
control panel as the activation of 2 simultaneous devices. In this
way, crossed relay L and crossed relay SL can be trigged directly
when you push this PUCAYEXT. From loop device capacity,
PUCAYEXT version is considered as a PUCAY.
The connection is made according to figure 2.
The PUCAY is conformant with EN 54-11 with the conformity mark awarded by AENOR.
Note: To determine the number of PUCAY it can be installed, consult the devices limit per
control panel table (Chapter 1.5)
Technical specifications PUCAY
Supply
24 – 35 V with polarity
Standby consumption
1 mA
Alarm consumption
5 mA
Indicator activation
red LED
Remote indicator output
No
Humidity
20% – 95% RH
Temperature
-10º + 50ºC
IP IP50