Digital fire detection control panel
COMPACT LYON PLUS
59
FIRE PROTECTION MANUFACTURER
C / Compositor Wagner, 8 –P.I. Can Jardí 08191 - RUBÍ (Barcelona) ESPAÑA.
Tlf.: +34 935 862 690 –
3.2.1.- Level 1 access.
3.2.1.1.- Activation of the control panel.
If the control panel is starting up correctly we see:
C D I D Z a f i r V x
( C )
C o f e m ,
S . A .
L o a d i n g . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
V.x corresponds the version number of the control panel’s software.
The control panel is looking at the previous configuration data:
R e c o v e r i n g
p r e v i o u s
c o n f i g u r a t i o n
Z o n e s :
[
]
R e l a y s :
[
]
U p d a t i n g
S y s t e m
[
]
The control panel is performing an automatic element search:
W a i t i n g
A u t o m a t i c
S e a r c h
. . . . . .
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -
M O D E
1 2
∕ 0 8 ∕ 0 6
S E A R C H I N G
1 0 : 2 9
When the control panel reaches at this screen and it remains, this confirms to us that the control
panel has been initialized correctly and that no alarms or faults of any type exist in the system.
Only the green LED is illuminated (Power). It is also possible that other screens appear indicating
anomalies of some type that are described in the following cases.
C D I C Z a f i r C o f e m s . a .
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -
M O D E
M O D E
1 2
∕ 0 8 ∕ 0 6
N I G H T
A U T O M A T I C
1 0 : 2 9
Anomalies during start-up:
1.
During the starting the possibility exists that memory I2C, where all the information keeps
from the control panel, fails. In this case, we have two posisibilities. One first that would
allow us to reinitiate the configuration of the control panel being restored the values of
factory (except labels of points and relays). Or one second, with that we could cancel the
resumption of the configuration. If after to have reinitiated the control panel it returns to
appear the message of “Failure I2C” it is that this one does not work correctly.
F a i l u r e
I 2 C
T h e
c o n f i g u r a t i o n
w i l l
r e s t a r t
P r e s s
E N T E R t o c o n t i n u e
P r e s s
E S C
t o
c a n c e l