Digital fire detection control panel
COMPACT LYON PLUS
31
FIRE PROTECTION MANUFACTURER
C / Compositor Wagner, 8 –P.I. Can Jardí 08191 - RUBÍ (Barcelona) ESPAÑA.
Tlf.: +34 935 862 690 –
1.5.4.10- Addressable sounder (SIRAY / SIRAYL / SIRAY+BSLC)
Microprocessed addressable sounder (with short-circuit isolator)
installed as another element inside the loop.
This sounder is manufactured in red plastic ABS.
It is a module with a single programming function respecting the
timing and combination of elements that activate it. This sounder is
configured as a relay being able to act as a sounder.
The SIRAYL and SIRAY+BSLC variants additionally emits light
signals, where, SIRAY+BSLC is EN 54-23 certified (visual alarm
devices). The fact that these sirens emit light specifically does not
affect the programming of control panel. For this reason, these
devices are programmed in the control panel as it was SIRAY.
The standard configuration of the sound of the siren is shown in
Figure 12
according to EN 54-3 (sounder). In the same figure the
standard configuration of the light signal in the socket of the
SIRAY+BSLC siren according to EN 54-23 (visual alarm device) is
shown.
It is allowed to change the selection of the tone and light signal, but
this operation affects the power consumption of the sounder, and
therefore consumption elements equivalence of the device.
Calculation can be made with the software of loop elements
capacity calculation.
It is shown the microswitchs position for standard and maximum
loudness at
figure 12
, also including light signal for standard or
maximum power emission.
Internal wiring and other microswitch positions should not be
modified.
Figure 12
. SIRAY / SIRAYL / SIRAY+BSLC Schematic connection
SIRAY
SIRAYL
SIRAY+BSLC