To avoid the dust entering in the sensors , wich may cause a performance degradation (A30XTA,
A30XHA , A30XHTCO, A50 series), the red cover protector should be put on sensors while there is
work on progress in that building.
Once everithing is operational, all covers from all sensors
SHOULD BE REMOVED
, otherwise they
will not work properly or not work at all.
A list must be made for each loop with the location, type and programming number of each element,
this programming number goes from 1 to the 65533, see the example in the following table:
Loop: 01
POINT
Programming no.
Label
Type
Notes
1
12757
ROOM 101
A30XHA
2
12432
ROOM 102
A30XHA
3
4767
BUTTON P1
PUCAY
4
6982
CORRIDOR P1
MDA1Y
DISCONNECT the 110~230V Voltage circuit and BATTERIES
before accessing the interior of the control panel.
2.2.1- Electrical supply network.
Power supply is 110
230V ±10% 50 - 60 Hertz. Connection will be made by means of 3 strands with a
minimum section of 1.5mm the connection of the earth cable to the terminal of the switched supply
being obligatory. The maximum consumption for a control panel of up to 2 loops is 70 W.
Connection will be made according to figure 13.
Figure 20.
Switched Mode Power Supply (SMPS) terminals input
DISCONNECT the 110~230V Voltage circuit and BATTERIES
before accessing the interior of the control panel.
Do not cut power to the control panel during the boot process.
Such action may cause malfunction of the unit.