Digital fire detection control panel
COMPACT LYON PLUS
69
FIRE PROTECTION MANUFACTURER
C / Compositor Wagner, 8 –P.I. Can Jardí 08191 - RUBÍ (Barcelona) ESPAÑA.
Tlf.: +34 935 862 690 –
VIEW LOOP INFORMATION: In this submenu we can see the number of elements that are in
the loop classified by type.
L O O P :
0 1
A 3 0 X H A
∕ S : 0 0 4
S I R A Y : 0 0 0
P O I N T S : 0 0 5
A 3 0 X T A
: 0 0 0
M D A x Y : 0 0 0
A 3 0 X H T C O : 0 0 0
M S T A Y : 0 0 0
M Y O A
: 0 0 0
P U C A Y
: 0 0 1
K M A Y : 0 0 0
SEARCH FOR LOOP POINTS: It detects elements in the installation and it shows a list the
same as the one above.
ASSIGN NUMBER TO POINT: To save the programming number of each point in the control
panel. The programming number is the identification number that each elements has (from 1 to
65533
and the same number may never be repeated in a loop
). The control panel must know
this programming number to identify the elements.
AUTOMATIC LOOP SETUP: Find the points of the loop and assigns a setup number to each
point in order of programming numbers starting with the smallest.
DELETE POINT: To delete a point that is no longer connected to the loop and is still
configured, delete the programming number and the label of the element.
REPLACE POINT: Replace one point in the loop by another. This is the appropriate option to
replace an element since it saves the label. Take into account that it is necessary to first
physically replace the element with the control panel disconnected, then start up the control
panel and lastly run this menu option
DELETE LOOP POINTS: To eliminate all the points configured in a loop both programming
numbers and labels.
3.2.3.3.2- Logic In/out configuration.....................................................................................Menu_18
In this menu we find various utilities such as auto-configuring relays, modifying relay activation parameters,
activation method, option to configure the list trigger, etc.