Digital fire detection control panel
COMPACT LYON PLUS
45
FIRE PROTECTION MANUFACTURER
C / Compositor Wagner, 8 –P.I. Can Jardí 08191 - RUBÍ (Barcelona) ESPAÑA.
Tlf.: +34 935 862 690 –
2- Installation
2.1- Control panel installation.
The control panel must be assembled on a vertical face. The lateral grooves in the control panel must be
left free for correct heat evacuation. The dimensions and pre-drilling for the cable input are in the
following figure.
Figure 19.
Control panel C-Lyon box
In order to manoeuvre the Cover holder, care must be taken with the ground cable connecting one of
its pin with a box pin or output circuit faston, and the connector of the CPU with the output circuit
(See figure 29, end of the manual chapter 4).
Any connection or movement of the control panel must be carried out with the panel disconnected,
both from the power supply, and from the batteries.
2.2- C-Lyon system connection
Connection of the
C-Lyon addressable system
will be carried out with
2 x 0.7 mm up to 2 x 2.5 mm
BRAIDED CABLE SCREENED HALOGEN FREE,
both the loops as well as the sounders, KMAY
connected elements, fault outputs and 30 volt auxiliary supplies.
The connection of the loop allows elements installed in the loop or in branches with wiring distances
between the elements and the control panel of lengths of up to 1500 meters.
Connection of the loop elements will be carried out in accordance with the schematics indicated in
figures 2, 3, 4, 5, 6, 7, 8, 9,10,11,12,13.