Figure 14: Typical Open Loop/Well Application
Pressure
Tank
Shut-Off
Valve
Boiler
Drains
Flow
Regulator
Water In
Water Out
Water
Control
Valve
Optional
Filter
P/T Plugs
Water Coil Low Temperature Limit Setting
For all open loop systems the -1.1°C FP1 setting (factory
setting-water) should be used to avoid freeze damage
to the unit. See “Low Water Temperature Cutout
Selection” in this manual for details on the low limit
setting.