DIP switch 2: Stage 2 Selection - provides selection of 

whether compressor has an “on” delay. If set to stage 

2, the compressor will have a 3 second delay before 

energizing. Also, if set for stage 2, the alarm relay will 

NOT cycle during test mode.

On = Stage 1. Off = Stage 2

DIP switch 3: Not Used.
DIP switch 4: DDC Output at EH2 - provides selection 

for DDC operation. If set to “DDC Output at EH2,” 

the EH2 terminal will continuously output the last fault 

code of the controller. If set to “EH2 normal,” EH2 will 

operate as standard electric heat output.

On = EH2 Normal. Off = DDC Output at EH2.

Note: Some CXM controls only have a 2 position DIP 

switch package. If this is the case, this option can be 

selected by clipping the jumper which is in position 

4 of SW1.

Jumper not clipped = EH2 Normal. Jumper clipped = 

DDC Output at EH2.

DIP switch 5: Factory Setting - Normal position is “On.” 

Do not change selection unless instructed to do so by 

the factory.

-Slow Flash = 1 fl ash every 2 seconds

-Fast Flash = 2 fl ashes every 1 second

-Flash code 2 = 2 quick fl ashes, 10 second pause, 2 

quick fl ashes, 10 second pause, etc.

-On pulse 1/3 second; off pulse 1/3 second

CXM Controls

CXM Control - 

For detailed control information, 

see CXM or DXM Application, Operation and 

Maintenance (AOM) manual (part # 97B0003N12 or part 

#97B0003N13).

Field Selectable Inputs - 

Test mode: Test mode 

allows the service technician to check the operation 

of the control in a timely manner. By momentarily 

shorting the test terminals, the CXM control enters a 

20 minute test mode period in which all time delays 

are sped up 15 times. Upon entering test mode, the 

status LED will fl ash a code representing the last fault. 

For diagnostic ease at the thermostat, the alarm relay 

will also cycle during test mode. The alarm relay will 

cycle on and off similar to the status LED to indicate a 

code representing the last fault, at the thermostat. Test 

mode can be exited by shorting the test terminals for 3 

seconds.

Retry Mode: If the control is attempting a retry of a 

fault, the status LED will slow fl ash (slow fl ash = one 

fl ash every 2 seconds) to indicate the control is in the 

process of retrying.

Field Confi guration Options -

 

Note: In the following 

fi eld confi guration options, jumper wires should be 

clipped ONLY when power is removed from the CXM 

control.

Water coil low temperature limit setting: Jumper 

3 (JW3-FP1 Low Temp) provides fi eld selection of 

temperature limit setting for FP1 of -1°C or -12°C] 

(refrigerant temperature).

Not Clipped = -1°C. Clipped = -12°C.

Air coil low temperature limit setting: Jumper 2 (JW2-

FP2 Low Temp) provides fi eld selection of temperature 

limit setting for FP2 of -1°C or -12°C (refrigerant 

temperature)

.  Note: This jumper should only be 

clipped under extenuating circumstances, as 

recommended by the factory.

Not Clipped = -1°C. Clipped = -12°C.

Alarm relay setting: Jumper 1 (JW1-AL2 Dry) provides 

fi eld selection of the alarm relay terminal AL2 to 

be jumpered to 24VAC or to be a dry contact (no 

connection).

Not Clipped = AL2 connected to R. Clipped = AL2 dry 

contact (no connection).

DIP Switches 

- Note: In the following fi eld 

confi guration options, DIP switches should only be 

changed when power is removed from the CXM 

control.

DIP switch 1: Unit Performance Sentinel Disable - 

provides fi eld selection to disable the UPS feature.

On = Enabled. Off = Disabled.

Table 6a: CXM/DXM LED And Alarm Relay Operations

CAUTION!

  Do not restart units without inspection 

and remedy of faulting condition. Equipment damage 
may occur. 

 

CAUTION!

 

Description of Operation

LED

Alarm Relay

Normal Mode

On

Open

Normal Mode with UPS Warning

On

Cycle (closed 5 sec., Open 25 sec.)

CXM is non-functional

Off

Open

Fault Retry

Slow Flash

Open

Lockout

Fast Flash

Closed

Over/Under Voltage Shutdown

Slow Flash

Open (Closed after 15 minutes)

Test Mode - No fault in memory

Flashing Code 1

Cycling Code 1

Test Mode - HP Fault in memory Flashing Code 2

Cycling Code 2

Test Mode - LP Fault in memory

Flashing Code 3

Cycling Code 3

Test Mode - LT1 Fault in memory Flashing Code 4

Cycling Code 4

Test Mode - LT2 Fault in memory Flashing Code 5

Cycling Code 5

Test Mode - CO Fault in memory Flashing Code 6

Cycling Code 6

Test Mode - Over/Under
shutdown in memory

Flashing Code 7

Cycling Code 7

Test Mode - UPS in memory

Flashing Code 8

Cycling Code 8

Test Mode - Swapped Thermistor Flashing Code 9

Cycling Code 9

Summary of Contents for Tranquility 16 Series

Page 1: ...ications 17 Ground Loop Heat Pump Applications 18 Ground Water Heat Pump Applications 20 Water Quality Standards 22 Electrical Line Voltage 23 Electrical Power Wiring 24 Electrical Power Low Voltage W...

Page 2: ...CLIMATE MAS TER WATER SO URCE H E AT PU MPS 2 ClimateMaster Water Source Heat Pumps Tran qui l i ty 16 TC Se ries R ev 2 5 July 2017 This Page Intentionally Left Blank...

Page 3: ...r Water Coil w CoatedAir Coil HEAT EXCHANGER OPTIONS C Copper Water Coil w Non CoatedAir Coil L LEFT RETURN RETURNAIR OPTIONS R RIGHT RETURN F FRONT RETURN VERTICAL009 030 B BACK DISCHARGE HORIZONTALO...

Page 4: ...physical damage to the units and contamination by foreign material Physical damage and contamination may prevent proper start up and may result in costly equipment clean up Examine all pipes fittings...

Page 5: ...and gloves when handling parts and servicing heat pumps Pre Installation Installation Operation and Maintenance instructions are provided with each unit Horizontal equipment is designed for installat...

Page 6: ...owaway mm 254 x 457 254x457 254 x 457 508 x 508 508 x 508 508 x 508 508 x 508 610 x 610 610 x 610 1 356 x 610 1 457 x 610 1 356 x 610 1 457 x 610 Weight Operating kg 47 48 52 69 72 86 89 92 99 119 126...

Page 7: ...electrical cables and other items that prohibit future removal of components or the unit itself 3 Use a manual portable jack lift to lift and support the weight of the unit during installation and se...

Page 8: ...uded on ClimateMaster commercial heat pumps for the purposes of holding the filter only For ducted return applications the filter rail must be removed and replaced with a duct flange or filter frame C...

Page 9: ...ccess Air Coil Front Front Front Front CCP CCP Notes 1 While clear access to all removable panels is not required installer should take care to comply with all building codes and allow adequate cleara...

Page 10: ...es are not pinched and not over sharp edges Adjust motor downward to tighten belt Raise or lower motor slide assembly with adjusting bolt and retighten 2 slide nuts Check for correct tension See Tensi...

Page 11: ...the minimum Each unit must be installed with its own individual trap and connection to the condensate line main or riser Provide a means to flush or blow out the condensate line DO NOT install units...

Page 12: ...stem To maximize sound attenuation of the unit blower the supply and return plenums should include internal fiberglass duct liner or be constructed from ductboard for the first few feet Application of...

Page 13: ...nd isolation The pad should be at least 10mm to 13mm in thickness Extend the pad beyond all four edges of the unit 2 Provide adequate clearance for filter replacement and drain pan cleaning Do not blo...

Page 14: ...e Except on units with front return air 3 ASP are removable panels that provide additional access to the units interior Clear access to ASP panels is not required and they are not to be used in place...

Page 15: ...local plumbing building codes Vertical units utilize a condensate hose inside the cabinet as a trapping loop therefore an external trap is not necessary Figure 10a shows typical condensate connections...

Page 16: ...orque for brass fittings is 41 N m If a torque wrench is not available tighten finger tight plus one quarter turn Tighten steel fittings as necessary Optional pressure rated hose assemblies designed s...

Page 17: ...em should be flushed to remove dirt piping chips and other foreign material prior to operation see Piping System Cleaning and Flushing Procedures in this manual The flow rate is usually set between 2...

Page 18: ...ntering loop temperatures drop below 5 C or where piping will be routed through areas subject to freezing antifreeze is required Alcohols and glycols are commonly used as antifreeze however your local...

Page 19: ...Balancing Valve Stainless steel braid hose with integral J swivel Building Loop Power Wiring Return Air upply Air Unit Hanger Ball Valve with optional integral P T plug 3 8 10mm threaded rods Unit Pow...

Page 20: ...rying two pressure gauges may be needed Adjust the valve until the desired flow of 2 0 to 2 6 l m per kW is achieved A second method of flow control requires a flow control device mounted on the outle...

Page 21: ...T ank Shut Off Valve Boiler Drains Flow Regulator Water In Water Out Water Control Valve Optional Filter P T Plugs Water Coil Low Temperature Limit Setting For all open loop systems the 1 1 C FP1 sett...

Page 22: ...ater temperature Chloride Levels 10 C 24 C 38 C Copper Cupronickel 20ppm NR NR 150 ppm NR NR 304 SS 400 ppm 250 ppm 150 ppm 316 SS 1000 ppm 550 ppm 375 ppm Titanium 1000 ppm 550 ppm 375 ppm Erosion an...

Page 23: ...ion during installation WARNING CAUTION Use only copper conductors for field installed electrical wiring Unit terminals are not designed to accept other types of conductors CAUTION WARNING WARNING Thi...

Page 24: ...ze Grnd Capacitor CAUTION Use only copper conductors for field installed electrical wiring Unit terminals are not designed to accept other types of conductors WARNING Disconnect electrical power sourc...

Page 25: ...fic terminal connections Review the appropriate AOM Application Operation and Maintenance manual for units with DDC controls Low Water Temperature Cutout Selection The CXM DXM control allows the field...

Page 26: ...20 and 21 illustrate typical slow closing water control valve wiring for Taco 500 series ClimateMaster P N AVM and Taco SBV series valves Slow closing valves take approximately 60 seconds to open very...

Page 27: ...sunlight drafts or on external walls The wire access hole behind the thermostat may in certain cases need to be sealed to prevent erroneous temperature measurement Position the thermostat back plate...

Page 28: ...IMATE MAS TER WATER SO URCE H E AT PU MPS 28 ClimateMaster Water Source Heat Pumps Tran qui l i ty 16 TC Se ries R ev 2 5 July 2017 Typical Wiring Diagram Single Phase 50 Hz TC Units with CXM Controll...

Page 29: ...THE SMAR T SOLUTI ON FOR E NE RGY E F F ICIEN CY 29 climatemaster com Tra nqui li ty 1 6 T C Series Rev 25 July 2017 Typical Wiring Diagram Single Phase 50 Hz TC Units with DXM Controller...

Page 30: ...ER WATER SO URCE H E AT PU MPS 30 ClimateMaster Water Source Heat Pumps Tran qui l i ty 16 TC Se ries R ev 2 5 July 2017 Typical Wiring Diagram Single Phase 50 Hz TC Units with CXM Controller and MPC...

Page 31: ...THE SMAR T SOLUTI ON FOR E NE RGY E F F ICIEN CY 31 climatemaster com Tra nqui li ty 1 6 T C Series Rev 25 July 2017 Typical Wiring Diagram Three Phase 50 Hz TC Units with CXM Controller...

Page 32: ...IMATE MAS TER WATER SO URCE H E AT PU MPS 32 ClimateMaster Water Source Heat Pumps Tran qui l i ty 16 TC Se ries R ev 2 5 July 2017 Typical Wiring Diagram Three Phase 50 Hz TC Units with DXM Controlle...

Page 33: ...SMAR T SOLUTI ON FOR E NE RGY E F F ICIEN CY 33 climatemaster com Tra nqui li ty 1 6 T C Series Rev 25 July 2017 Typical Wiring Diagram Three Phase 50 Hz TC Units with DXM Controller and MPC DDC Contr...

Page 34: ...g a retry of a fault the status LED will slow flash slow flash one flash every 2 seconds to indicate the control is in the process of retrying Field Configuration Options Note In the following field c...

Page 35: ...ides field selection for low pressure input to be normally closed or normally open Not Clipped LP normally closed Clipped LP normally open DIP Switches Note In the following field configuration option...

Page 36: ...the fan speed relay will remain off during cooling stage 2 In normal mode the fan speed relay will turn on during cooling stage 2 On Normal fan mode Off Dehumidification mode 1 6 DDC output at EH2 DIP...

Page 37: ...lt If the low pressure switch is open for 30 seconds prior to compressor power up it will be considered a low pressure loss of charge fault The low pressure switch input is bypassed for the initial 12...

Page 38: ...rrent status of the CXM control The LED can display either the current CXM mode or the last fault in memory if in test mode If there is no fault in memory the LED will flash Code 1 when in test mode T...

Page 39: ...or indoor installation only Never install units in areas subject to freezing or where humidity levels could cause cabinet condensation such as unconditioned spaces subject to 100 outside air Power Sup...

Page 40: ...al the rate of bleed 4 Refill the system and add trisodium phosphate in a proportion of approximately 1 2 kg per 750 l of water or other equivalent approved cleaning agent Reset the boiler to raise th...

Page 41: ...ty of hoses and fittings see table 3 System flushing Verify that all hoses are connected end to end when flushing to ensure that debris bypasses the unit heat exchanger water valves and other componen...

Page 42: ...should be between 8 C and 14 C g Turn thermostat to OFF position A hissing noise indicates proper functioning of the reversing valve 6 Allow five 5 minutes between tests for pressure to equalize befo...

Page 43: ...28 40 6 31 5 26 9 23 4 024 0 19 15 2 11 6 9 6 8 3 0 28 27 6 22 2 19 3 17 2 0 38 49 6 40 6 35 8 32 4 030 0 24 9 0 6 1 4 8 4 1 0 35 15 8 12 5 10 3 9 6 0 47 28 9 23 2 20 17 9 036 0 28 12 4 9 6 8 3 6 9 0...

Page 44: ...filter Washable high efficiency electrostatic filters when dirty can exhibit a very high pressure drop for the fan motor and reduce air flow resulting in poor performance It is especially important to...

Page 45: ...heck for piping slope away from unit Check slope of unit toward outlet Poor venting Check vent location X Moisture on sensor Check for moisture shorting to air coil X X Plugged air filter Replace air...

Page 46: ...place Check fan motor operation and air flow restrictions Too high of external static Check static vs blower table X Reduced or no water flow in cooling Check pump operation or valve operation setting...

Page 47: ...OIL C C FP2 HEATING LIQUID LINE C EXPANSION VALVE AIR COIL C C bar SAT bar SAT C C C C WATER IN WATER OUT kPa kPa C C WATER IN WATER OUT kPa kPa Look up pressure drop in I O M or spec catalog to deter...

Page 48: ...nsuf cient performance as a result of insuf cient or incorrect system design or the improper application installation or use of CM s products or 14 Electricity or fuel costs or any increases or unreal...

Page 49: ...THE SMAR T SOLUTI ON FOR E NE RGY E F F ICIEN CY 49 climatemaster com Tra nqui li ty 1 6 T C Series Rev 25 July 2017 Notes...

Page 50: ...CLIMATE MAS TER WATER SO URCE H E AT PU MPS 50 ClimateMaster Water Source Heat Pumps Tran qui l i ty 16 TC Se ries R ev 2 5 July 2017 Notes...

Page 51: ...THE SMAR T SOLUTI ON FOR E NE RGY E F F ICIEN CY 51 climatemaster com Tra nqui li ty 1 6 T C Series Rev 25 July 2017 Notes...

Page 52: ...f each product at the time for order may be changed without notice and may not be as described herein Please contact ClimateMaster s Customer Service Department at 1 405 745 6000 for specific informat...

Reviews: