Accessory functions
to
select accessory functions
such as coolant fl ush
or pressure test using
nitrogen.
Settings
to set the basic
parameters (date and time,
language, etc.).
Options
to access optional
settings or functions
.
to print the data
stored in the unit or the
data from the last service
cycle.
ENTRER
ENTRER
ENTRER
ENTRER
Remarque:
Libération des gaz non condensables
If the theoretical value of the gas pressure (see above n. 3) - calculated
according to its temperature (see above n. 2) - is signifi cantly lower than
the value of the tank pressure (see central manometer), the gas may
be mixed with non-condensable gases (NCG). In this case, the machine
automatically releases the pressure through the relief valve. Alternatively,
the user can manually pull the ring on the max pressure valve to release
the NCGs until both the theoretical and actual pressure are met.
Note:
If the theoretical value of the gas pressure, on the other hand, is
higher than the value indicated by the tank pressure gauge, the amount
of gas in the tank is too low.
2
Accessory functions
Internal recirculation
Settings
Date/time
Print recovered gas
Print a report
Print a report