24
−
OPERATION
2
●
Switch output
Having 2 pieces of switch output, 7 operation patterns and stop of operation can be set.
No.
Operation pattern
Description
Operation waveform
LCD display
1
Switch output OFF
Switch output OFF
2
Window operation[1]
(Range inside ON)
Note1
The switch turns ON when
the level is within the des-
ignated flow rate range.
3
Window operation[2]
(Range out ON)
Note1
The switch turns ON when
the level is not within the
designated flow rate range.
4
Hysteresis operation[1]
(Flow rate small side ON)
ON when lower than set
point. Hysteresis can be
arbitrarily set.
5
Hysteresis operation[2]
(Flow rate large side ON)
ON when higher than set
point. Hysteresis can be
arbitrarily set.
6
Integrated output[1]
(
On when higher than
set integration
)
The switch turns ON at the
set integrated flow.
7
Integrated output[2]
(
Off when higher than
set integration
)
The switch turns OFF at the
set integrated flow.
8
Integrated pulse
The integrated pulse is
output during integration.
See specifications for de-
tails on the pulse output
rate.
Note1: Hysteresis is provided on upper and lower limit of window operation automatically.
The hysteresis can be fixed in 8 steps. Refer to <2.5.8.Hysteresis fixed value selection> in <De-
tailed setting mode>.
Note2:Refer to <Pulse output rate> in <4.1. Specifications>.
Note3: Output (OUT1,2) display blinks when the multiplication pulse output is set.
Flow rate
ON
OFF
Lower limit
Upper limit
Flow rate
ON
OFF
Upper limit
Lower limit
Flow rate
ON
OFF
Lower limit
Upper limit
Flow rate
ON
OFF
Upper limit
Lower limit
Integrated
flow rate
ON
OFF
Set point
Integrated
flow rate
ON
OFF
Set point
Integrated
flow rate
ON
OFF
Pulse rate
Note2
40msec
Flow rate
ON
OFF
Discontinue