[2]

 

Installation 

Arrange piping so that the flow 

direction agrees with the direction 
of the arrow indicated on the   
sensor body. 

 

Flash the pipe to remove foreign substances and swarf, etc., in inside of 

pipe before piping. 

When piping a sensor, do not apply excessive screw-in and load torques to the 

port. 
When piping, apply a spanner on the metal section not to apply forces 
onto the resin section. 

 
 
 
 
 
 
 
 
 
 
 

When piping, care must be taken that sealing tape and adhesive must 

not enter into the inside. 

If a push-in joint is used, the tube must be inserted certainly. Pulls the 

tube to check that the tube not be come out. 

This product can be installed with any attitude; vertical, horizontal, right 

or left. 
The tightening torque for screws should be 0.5N

m. 

                     

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

How to panel mount

 

[3] Piping 

Power supply voltage and outputs must be used with the specified 

voltage. Applying the voltage more than specified voltage may cause 
malfunction, damage of sensor, electric shock or fire.   
Do not apply load more than the rated output. Damage or fire of the 
output may be caused. 

For wiring, stop control unit/machinery and equipment, and turn off the 

power supply. 

This product and wiring must be installed as far away as possible from noise 

source such as strong electric line, etc. Take other countermeasures for a 
surge on the power supply line. 

Do not short-circuit a load, or causing damage or burn. 

Line color must be checked when wiring. Check the wiring color with handling 

precaution, since improper wire connection may result in damage, failure or 
malfunction of the sensor. 

Use DC safety power supply thoroughly insulated from the AC primary side for 

a power supply for the metal body (stainless steel and aluminum bodies) type, 
while connecting or - side on the power supply to F.G. 

After the connectors are inserted, lay the connector covers over the 

connectors.

 

Make sure that stress by forcible bend of pulling is not applies 

directly to the sensor cable joint. 

 

Example of internal circuit and load connection

 

NPN output

   

Model no.: FSM2 -N[ ]-[ ] 

<CH2 function selected switch output> 

 
 
 
 
 
 
 
 
 
 
 
 

<CH2 function selected external input> 

 
 
 
 
 
 
 
 
 
 
 
 

PNP output

   

Model no.: FSM2 -P[ ]-[ ] 

<CH2 function selected switch output> 

 
 
 
 
 
 
 
 
 
 

 
 
 

<CH2 function selected external input> 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

[1] [2] [3] 

The panel bessel is inserted 
from the front side of the 
panel.   

The panel Bessel is inserted 
from the back side of the 
panel, and holding with the 
screw. 

The separation indicator is 
inserted from the back side of 
the panel. 

[4] [5] 

The panel holder is inserted 
from the back side of the 
panel. 

The  panel holder  is 
pushed until the sensor is 
firmly fixed, and connector is 
connected. 

Note: 
・ Please  do  the  piping  work 

before  it  works  of  the  panel 
mount, and please do not add 
the  stress  to  parts  of  the 
panel mount.

 

 

 Please fix by the tightening 

torque of 0.06N

m when 

you fix the panel bessel 
suppression. 

 

Set screw 

Tightening torque 

N

Rc1/8 

3

Rc1/4 

6

 

Bracket (separate sales)   
Model no. : FSM2-LB1 
Port size: Push-in joint 

φ

4

6

8

10 

             

Rc1/8

Rc1/4 

Main circuit 

Load 

Load

Load

Brown (Power )

Gray (Analog output) 

Black (CH1) 

Switch output 1 

White (CH2) 

Switch output 2 

Blue (Power supply -) 

+
-

1

Main circuit 

Load 

Load

White (CH2) 

External input 

+
-

Brown (Power )

Black (CH1) 

Switch output 1 

Gray (Analog output) 

Pin No.

Line color 

Content 

[1] 

Brown 

Power supply (DC 12 to 24V, DC 24V) 

[2] 

Black 

CH1(Switch output 1: max50mA) 

[3] White CH2(Switch output 2: max50mA    or    External input

[4] Gray 

Analog voltage output : DC 1 to 5V   

       Connected load impedance 50k

 and over) 

Analog current output : DC 4 to 20mA 

       Connected load impedance 300

 or less) 

[5] Blue 0V 

(GND) 

※Analog output voltage output type  R:about1kΩ 

                    Current  output type R:about100Ω 

[1] [2] [3] [4] [5]

(FSM2 side) 

Vertical mount(with bottom thread) 

Horizontal mount 

(with through hole) 

Bracket mount (with bracket) 

Main circuit 

Load 

Load

Load

Brown (Power )

Gray (Analog output) 

+
-

Black (CH1) 

Switch output 1 

White (CH2) 

Switch output 2 

Blue (Power supply -) 

Panel mount 

Panel mount kit Model no. 

:FSM2-KHS-N 

Panel bessel suppression 

Screw 

Panel 

Panel bessel 

Sensor 

Panel holder 

Main circuit 

Load 

Load

Brown (Power )

Gray (Analog output) 

+
-

Black (CH1) 

Switch output 1 

White (CH2) 

External input 

Blue (Power supply -) 

Panel bessel

Panel bessel suppression 

Screw

Panel holder 

Sensor 

-2- 

R

 

R

 

R

 

Blue (Power supply -) 

R

 

Discontinue

Summary of Contents for Rapiflow FSM2-N Series

Page 1: ...M2 N series Integrated needle valve type Read this instruction manual carefully before using this product particularly the section describing safety Retain this instruction manual with the product for further consultation whenever necessary 2 n d E D I T I O N Discontinue ...

Page 2: ...vided but damage could result if the needle is turned too far Power supply voltage and outputs must be used with the specified voltage Applying the voltage more than specified voltage may cause malfunction damage of sensor electric shock or fire Do not apply load more than the rated output Damage or fire of the output may be caused For wiring stop control unit machinery and equipment and turn off ...

Page 3: ...2 function selected switch output CH2 function selected external input PNP output Model no FSM2 P CH2 function selected switch output CH2 function selected external input 1 2 3 The panel bessel is inserted from the front side of the panel The panel Bessel is inserted from the back side of the panel and holding with the screw The separation indicator is inserted from the back side of the panel 4 5 ...

Page 4: ...ure 101kPa calculation value Eco mode setting Current consumption can be lowered When the product is left for 1 min without any operation it s shift to eco mode Reset setting Return to default settings factory settings 5 How to operate 5 1 Normal mode Displaying the integrated flow Note Integration is reset with the external input See auto reference function Note Integration is also reset or Integ...

Page 5: ...steresis operation 1 Hysteresis operation 2 Integrated output 1 Integrated output 2 Integrated pulse CH1 operation mode change Press once determination CH1 ON OFF data setting mL min Lower limit data setting Upper limit data setting Count UP Count down Press once determination CH2 operation mode change Set same as CH1 CH2 ON OFF data setting Set same as CH1 Press once determination Press once dete...

Page 6: ...lue At instantaneous flow rate display press key for 8 sec to enter to detailed setting mode To auto reference setting display To response time setting display To display speed setting display To sub display setting display To displayed color setting display To hysteresis fixed value setting display To flow rate unit setting display To eco mode setting display To reset setting display To model num...

Page 7: ...display To instantaneous flow rate display Press once determination Input point mL min Lower limit mL min Upper limit mL min Initial value 0 0 1st 123 0 123 2nd 234 123 234 3rd 45 45 234 4th 345 45 345 5th 456 345 456 Display speed setting display Setting of display speed 250msec 500msec 1000msec To instantaneous flow rate display Press once determination Press or key to select display speed Press...

Page 8: ... by noise Keep FSM2 main body and cable away from the noise source Sensor chip is broken Replace FSM2 Foreign matter sticking to sensor chip Replace FSM2 Poor precision Malfunction caused by noise Keep FSM2 main body and cable away from the noise source Reduce pulsation by installing tank etc Change the response time Change the display speed Pulsation of air Fault in power source not enough voltag...

Page 9: ...splay Dual 2 4 digit 7 segm ent Two color LCD Flow rate range 3 F 0 to 500 mL min 0 to 1000 mL min 0 to 2 00 L m in 0 to 5 00 L m in 0 to 10 00 L m in 0 to 20 0 L m in 0 to 50 0 L m in 0 to 100 0 L m in 0 to 200 L m in Flow rate display Note 1 2 Display resolution 1m L m in 0 01L m in 0 1L m in 1L m in Flow rate range 9999999m L 99999 99L 999999 9L 9999999L Display resolution 1m L 0 01L 0 1L 1L In...

Page 10: ...e8 50m A or less Lead wire φ3 7 AW G26 5 Functions Flow rate display flow rate display peak hold switch output and analog output Outside diam eter of insulator is Φ1 0 Installation attitude Both vertical and horizontal Strait piping section Not required Protective structure Note 9 IEC standards IP40 Protective circuit Note5 Power supply and switch output reverse connection protections and switch o...

Page 11: ...o FSM2 LB1 Model No FSM2 KHS N How to panel mount Panel hold matching Fig Plate thickness t0 8 to 6 Single mount Sticking mount 2 M3depth5 Model No Port size Dimension A FSM2 H04 Φ4 push in 89 FSM2 H06 Φ6 push in 90 Model No Port size Dimension A FSM2 H08 Φ8 push in 101 6 FSM2 H10 Φ10 push in 113 1 2 M3depth5 A B Model No Dimension A Dimension B FSM2 H04 H06 S06 N 28 5 40 5 FSM2 H08 H10 S08 N 30 0...

Page 12: ...ncluded H10 Φ4 push in resin K Inspection results included S06 Rc1 8 stainless S08 Rc1 4 stainless 10 Needle valve 11 Clean N Needle valve Blank none P70 Particle occurrence prevention P80 Oil treatment prohibited Combination of flow rate range port size and working fluid 5 Port size body material H04 H06 H08 H10 S06 S08 005 010 020 050 100 200 500 101 4 Flow rate range 201 Table for clean specifi...

Reviews: