Dryer Installation with Separate Exhaust (Preferred) (Illustration)
DRYER INSTALLATION WITH SEPARATE EXHAUST
(PREFERRED)
For Exhaust Duct less than 14 feet (5 m) and 2 elbows equivalent
and less than 0.3 (8 mm) inches static pressure.
NEVER exhaust the dryer into a chimney.
NEVER install wire mesh screen over the exhaust or make-
up air area.
NEVER exhaust into a wall, ceiling, or concealed space.
1. Make-up air opening from outside the building may enter the
enclosure from the top or side walls.
(See Dryer Make-Up
Air Requirements Chart)
2. Enclosure (plenum) with service door. This separates the
dryer air from the room comfort air. If dryers use room air
instead of outside air, the heat loss can be another 25 Btu/h
(6.3 kcal/h) for each cubic foot per minute (cfm) used.
EXAMPLE:
A 125 lb. dryer with 2000 cfm (3400 m
3
/h) =
heat loss of 50,000 Btu/h (12,600 kcal/h).
3. Zero inches clearance to combustible material allowed on
sides and at points within 4 inches (102 mm) of front on top.
4. Heat loss into laundry room from dryer fronts
only
is about
60 Btu/h (15.2 kcal/h) per square foot.
DRYER INSTALLATION
WITH SEPARATE
EXHAUST (PREFERRED)
Summary of Contents for HD125
Page 9: ...Page 9 125 lb General Dimensions Illustration...
Page 10: ...Page 10 125 lb Steam Heated Dryer Dimensions Illustration...
Page 14: ...Page 14 Gas Loop Piping and Gas Supply Piping System Illustrations...
Page 18: ...Page 18 Steam Piping Installation Illustration...
Page 20: ...Page 20 Dryer Installation with Multiple Exhaust Illustration...
Page 27: ...Page 27 Two Timer Models Figures 1 2 and 3 Illustrations...
Page 35: ...Page 35 DIRECTSPARK IGNITIONOPERATION FLOW CHART...
Page 37: ...Page 37 Burner Air Inlet Adjustment with Illustration BURNERAIRINLET ADJUSTMENT...
Page 38: ...Page 38 Basket Alignment for 125 lb Dryers Illustrations...
Page 66: ...Page 66...