51
Instruction Manual
line-M
Hold down key
to set
full scale
(FULL SCALE),
whose final analogue output value is 20 mA or 10 V.
Use keys
and
to modify the digit's value.
Press key
to skip through the digits.
Zero and Full Scale:
Minimum value:
- 32765.
Maximum value:
32765.
Hold down key
to validate the value.
Use key
to skip to the next programming point.
6�5�- MODBUS MEMORY MAP line-M-4IO-A
Note:
For all modbus map parameters,
SLOT1 corresponds to the first expansion module connected to
the right-hand side of the
line-CVM-D
and SLOT2 corresponds to the second connected module.
6�5�1�- ANALOGUE INPUT
The
Function 0x04
, is implemented for these variables.
Table 27: Modbus Memory Map: Analogue Input Value�
Parameter
Format
Address
SLOT 1
SLOT 2
Analogue Input Value 1
Int [32]
D390 - D391
D778 - D779
Analogue Input Value 2
Int [32]
D392 - D393
D77A - D77B
Analogue Input Value 3
Int [32]
D394 - D395
D77C - D77D
Analogue Input Value 4
Int [32]
D396 - D397
D77E - D77F
6�5�2�- DEVICE CONFIGURATION VARIABLES
The following functions are used for these variables:
Function 0x03
: register readout.
Function 0x10
: Writing multiple registers.
Summary of Contents for line-LM20I-TCP kit
Page 1: ...INSTRUCTION MANUAL Expansion modules for the line CVM and line EDS devices M239B01 03 20B...
Page 2: ...2 line M Instruction Manual...
Page 95: ...95 Instruction Manual line M 118 105 45 35 7 90 44 70 Figure 47 line LM20I TCP kit dimensions...
Page 105: ...105 Instruction Manual line M 16 CE CERTIFICATE...
Page 106: ...106 line M Instruction Manual...
Page 107: ...107 Instruction Manual line M...