Table 18 (Continuation): Modbus Memory Map: Relay outputs�
Configuration parameters
Format
Address
Valid data range
Default value
Latch
Bool
C36D
0:
No
- 1:
Yes
Latching time
Uint [16]
C36E
0... 65499 s
0 s
Output unlocking
(12)
Bool
C684
0
0
Manual Operation:
Output status
(11) (12)
Bool
C68D
ON (Connect output):
FF00
OFF (Disconnect output):
0000
0
Relay output 3
Variable
Uint [16]
C378
0:
Manual -
-
0
Maximum value
(13)
/
Energy per pulse
(14)
Float [32]
C37A-C37B
Depends on the selected variable
-
Minimum value
(13)
Float [32]
C37C-C37D
Depends on the selected variable
-
Connection delay
Uint [16]
C37E
0... 65499 s
0 s
High level pulse width
(14)
0... 999 ms (x10)
Disconnection delay
Uint [16]
C37F
0... 65499 s
0 s
Low level pulse width
(14)
0... 999 ms (x10)
Hysteresis
Uint [16]
C380
0... 99%
0%
Contact status
Uint [16]
C379
0:
Normally open
-
1:
Normally closed
0
Latch
Bool
C381
0:
No
- 1:
Yes
Latching time
Uint [16]
C382
0... 65499 s
0 s
Output unlocking
(11)
Bool
C698
0
0
Manual Operation:
Output status
(11) (12)
Bool
C6A1
ON (Connect output):
FF00
OFF (Disconnect output):
0000
0
Relay output 4
Variable
Uint [16]
C38C
0:
Manual -
-
0
Maximum value
(13)
/
Energy per pulse
(14)
Float [32]
C38E - C38F
Depends on the selected variable
-
Minimum value
(13)
Float [32]
C390 - C391
Depends on the selected variable
-
Connection delay
Uint [16]
C392
0... 65499 s
0 s
High level pulse width
(14)
0... 999 ms (x10)
Disconnection delay
Uint [16]
C393
0... 65499 s
0 s
Low level pulse width
(14)
0... 999 ms (x10)
Hysteresis
Uint [16]
C394
0... 99%
0%
Contact status
Uint [16]
C38D
0:
Normally open
-
1:
Normally closed
0
Latch
Bool
C395
0:
No
- 1:
Yes
Latching time
Uint [16]
C396
0... 65499 s
0 s
Output unlocking
(11)
Bool
C6AC
0
0
Manual Operation:
Output status
(11) (12)
Bool
C6B5
ON (Connect output):
FF00
OFF (Disconnect output):
0000
0
SLOT 2
Relay output 1
Variable
Uint [16]
C738
0:
Manual -
-
0
Maximum value
(13)
/
Energy per pulse
(14)
Float [32]
C73A-C73B
Depends on the selected variable
-
Summary of Contents for line-LM20I-TCP kit
Page 1: ...INSTRUCTION MANUAL Expansion modules for the line CVM and line EDS devices M239B01 03 20B...
Page 2: ...2 line M Instruction Manual...
Page 95: ...95 Instruction Manual line M 118 105 45 35 7 90 44 70 Figure 47 line LM20I TCP kit dimensions...
Page 105: ...105 Instruction Manual line M 16 CE CERTIFICATE...
Page 106: ...106 line M Instruction Manual...
Page 107: ...107 Instruction Manual line M...