55
Instruction Manual
line-M
6�6�- TECHNICAL FEATURES: line-M-4IO-A
General features
Maximum power of the module
3 W
Installation category
CAT III 300V
Refresh time
(19)
200 ms
Response time (outputs)/Detection time (inputs)
(19)
< 200 ms
(19)
With the module connected to a
line-CVM
.
Analogue inputs
Quantity
4
Type of measure
Current
Nominal input range
0 - 20 mA, 4 - 20 mA (Programmable)
Input impedance
150 Ω
Permissible maximum current to the input
22 mA
Analogue outputs
Quantity
4
Maximum internal voltage
12 V
Linearity
< 1%
DAC resolution
4096 points
Analogue outputs in current mode
Nominal output range
0 - 20 mA, 4 - 20 mA (Programmable)
Maximum load resistance
300 Ω
Analogue outputs in voltage mode
Nominal output range
0 - 10 V
Maximum load resistance
5000 Ω
Accuracy
Inputs
Outputs
0��� 20 mA
0��� 20 mA
0��� 10 V
Accuracy
< 1 %
1%
1%
Accuracy range in relation to Full Scale
5... 100%
0,5... 100%
2... 100%
Measurement range in relation to Full Scale
1... 100%
0,1... 100%
0,2... 100%
User interface
LED
9 LEDs
Environmental features
Operating temperature
-10ºC ... + 50ºC
Storage temperature
-20ºC ... +70ºC
Relative humidity (non-condensing)
5... 95%
Maximum altitude
2000 m
Protection degree
IP30, Front: IP40,
Mechanical features
Terminals
1... 12,
2.5 mm
2
≤ 0.4 Nm, M2.5
flat
Dimensions
(mm)
Weight
153 g.
Summary of Contents for line-LM20I-TCP kit
Page 1: ...INSTRUCTION MANUAL Expansion modules for the line CVM and line EDS devices M239B01 03 20B...
Page 2: ...2 line M Instruction Manual...
Page 95: ...95 Instruction Manual line M 118 105 45 35 7 90 44 70 Figure 47 line LM20I TCP kit dimensions...
Page 105: ...105 Instruction Manual line M 16 CE CERTIFICATE...
Page 106: ...106 line M Instruction Manual...
Page 107: ...107 Instruction Manual line M...