51
Instruction Manual
line-CVM-D32
6�2�2�- OVERVOLTAGE AND GAPS
This screen enables threshold values for detecting overvoltage and gaps.
SWELL
DIP
110.0
90.0
%
%
SETUP
EVQ
Hold down key
to set the threshold value for the detection of an
overvoltage,
in % of nominal
voltage value
(SWELL)
.
Hold down key
to set the threshold value for the detection of a
gap,
in % of nominal voltage value
(DIP)
.
Use keys
and
to modify the digit's value.
Press key
to skip through the digits.
Hold down key
to validate the value.
Overvoltage:
Minimum value:
100.0 %
Maximum value:
150.0 %
Gap:
Minimum value:
50.0 %
Maximum value:
97.0 %
Use key
to skip to the next programming point.
6�2�3�- INTERRUPTION AND HYSTERESIS VALUE
This screen enables configuration of threshold values for the detection of quality parameter interrup-
tions and hysteresis values.
INTERRUPTION
HISTERESIS
SETUP
EVQ
10.0
2.0
%
%
Hold down key
to set the threshold value for the detection of an
interruption,
in % of nominal
voltage value
(INTERRUPTION)
.
Hold down key
to set the hysteresis value for each of the quality parameters
(HYSTERESIS)
.
Use keys
and
to modify the digit's value.