92
line-CVM-D32
Instruction Manual
be a multiple of 60, i.e. if the programmed value contains the number 60, an integer of the number.
(14)
Parameter not configurable via display.
(15)
Functions 0x01 and 0x05
are used
for
this variable
.
7�3�10�2�- Quality parameters
Table 30: Modbus Memory Map: Quality parameters�
Quality parameters
Configuration variable
Format
Address
Valid data range
Default value
Nominal voltage
Float [32]
271C-271D
50.0 .... 2000000.0 V
230.00 V
Nominal frequency
Uint [16]
2720
50-60Hz;
50 Hz
Overvoltage (swell)
Float [32]
2ABC-2ABD
100.0 ... 150.0 %
110.0 %
Gap (Dip)
Float [32]
2ABE-2ABF
50.0 ... 97.0 %
90.0 %
Outage (Interruption)
Float [32]
2AC0-2AC1
1.0 ... 20.0 %
10.0%
Overvoltage hysteresis
Float [32]
2AC4-2AC5
0.0 ... 100.0 %
2.0 %
Gap hysteresis
Float [32]
2AC6-2AC7
0.0 ... 100.0 %
2.0 %
Interruption hysteresis
Float [32]
2AC8-2AC9
0.0 ... 100.0 %
2.0 %
7�3�10�3�- Device clock
Table 31: Modbus Memory Map: Device clock�
Device clock
Configuration variable
Format
Address
Valid data range
Default value
Date format
Uint [16]
280F
0
: mm/dd/yy
1
: dd/mm/yy
1
Date and Time
Uint [32]
283C
Date and time are given in Epoch format
7�3�10�4�- Communications
Table 32: Modbus Memory Map: Communications�
Communications
Configuration variable
Format
Address
Valid data range
Default value
Peripheral number
Uint [16]
2739
1... 255
1
Transmission speed
Uint [32]
273A-273B
4800, 9600, 19200, 38400,
57600, 115200
9600
Data format
Uint [16]
273C
0
: 8N1 -
1
: 8E1 -
2
: 8O1 -
3
: 8N2 -
4
: 8E2 -
5
: 8O2
0
Measurement parameter
calculation time
Uint [16]
1389
0
: 200 ms -
1
: 3 s -
2:
Programmed value
(17)
1
Maximum and Minimum
parameter calculation time
(16)
Uint [16]
138A
0
: 200 ms -
1
: 3 s -
2:
Programmed value
(17)
1
(16)
Parameter not configurable via display.
(17)
Value programmed in the
Aggregation Period
variable.