Digital inputs
Quantity
2
Type
NPN
Insulation
2000 V
Max� current in short circuit
4 mA
Max� voltage in open circuit
17 V
Digital outputs
Quantity
2
Type
NPN
Maximum voltage
24 V
Maximum current
50 mA
Maximum frequency
16 impulses / sec
Pulse width
300 ms to 400 ms
Communications
Modbus RTU
BACnet
Bus
RS-485
MS/TP
Protocol
Modbus RTU
BACnet
Baud rate
9600 - 19200 - 38400 bps
Stop bits
1 - 2
1
Parity
without - even - odd
without
User interface
Display
LCD Custom COG
Keyboard
3 keys
LED
2 LED
Environmental features
Operating temperature
-25ºC ... +70ºC
Storage temperature
-25ºC ... +75ºC
Relative humidity (non-condensing)
5 ... 95%
Maximum altitude
2000 m
Protection degree IP
IP20, Front panel: IP54
Protection degree IK
IK08
Pollution degree
2
Use
Indoor
Mechanical features
Terminals
1, 2, 14 ... 17, 9 ... 13, 18 ... 25
0.2 ... 2.5 mm
2
0.5 ... 0.6 Nm
M3
3 ... 8
0.2 ... 1.5 mm
2
0.2 ... 0.25 Nm
M2
Dimensions
( Figure 24)
96 x 96 x 67.2 mm
Weight
353 g.
Surround
Self-extinguishing V0 plastic
Attachment
Panel
91
Instruction Manual
CVM-C11