Press key
for 3 seconds to edit the value. The
icon appears at the top of the screen.
To enter or modify the value, press the
key repeatedly, increasing the value of the flashing digit.
When the desired value is shown on the screen, move onto the next digit by pressing the key
to
modify the other values.
When you enter the code of a variable on the display, the symbols for that variable will be activated.
To validate the data, press
for 3 seconds and the
icon will disappear from the display.
Configuration values
Note:
Set the value to
000
if you do not wish to program a variable.
Table 51: Parameter codes used to program digital outputs�
Parameter
Tariff
Code
Tariff
Code
Tariff
Code
Tariff
Code
Consumed Active Energy
T1
49
T2
70
T3
91
total
112
Generated Active Energy
T1
59
T2
80
T3
101
total
122
Consumed Inductive Reactive Energy
T1
51
T2
72
T3
93
total
114
Generated Inductive Reactive Energy
T1
61
T2
82
T3
103
total
124
Consumed Capacitive Reactive Energy
T1
53
T2
74
T3
95
total
116
Generated Capacitive Reactive Energy
T1
63
T2
84
T3
105
total
126
Consumed Apparent Energy
T1
55
T2
76
T3
97
total
118
Generated Apparent Energy
T1
65
T2
86
T3
107
total
128
Consumed CO
2
Emissions
T1
56
T2
77
T3
98
total
119
Generated CO
2
Emissions
T1
66
T2
87
T3
108
total
129
Consumption Cost
T1
57
T2
78
T3
99
total
120
Generation Cost
T1
67
T2
88
T3
109
total
130
No. of hours
T1
68
T2
89
T3
110
total
131
If you have selected a parameter from
or
the subsequent programming steps are the
same as for alarm relay 1, see (
PROGRAMMING THE ALARM RELAY 1”
).
If you have selected a parameter from
the subsequent programming steps are:
6�27�1�- KILOWATTS PER PULSE
In this section, the kilowatts per pulse of digital output T1 are programmed.
63
Instruction Manual
CVM-C11