Table 69 (Continuation) : Modbus memory map (Table 4)�
Parameter
L1 Current
L2 Current
L3 Current
Units
4th Order harmonic
A8C
AAC
ADC
% x 10
5th Order harmonic
A8D
AAD
ACD
% x 10
6th Order harmonic
A8E
AAE
ACE
% x 10
7th Order harmonic
A8F
AAF
ACF
% x 10
8th Order harmonic
A90
AB0
AD0
% x 10
9th Order harmonic
A91
AB1
AD1
% x 10
10th Order harmonic
A92
AB2
AD2
% x 10
11th Order harmonic
A93
AB3
AD3
% x 10
12th Order harmonic
A94
AB4
AD4
% x 10
13th Order harmonic
A95
AB5
AD5
% x 10
14th Order harmonic
A96
AB6
AD6
% x 10
15th Order harmonic
A97
AB7
AD7
% x 10
16th Order harmonic
A98
AB8
AD8
% x 10
17th Order harmonic
A99
AB9
AD9
% x 10
18th Order harmonic
A9A
ABA
ADA
% x 10
19th Order harmonic
A9B
ABB
ADB
% x 10
20th Order harmonic
A9C
ABC
ADC
% x 10
21st Order harmonic
A9D
ABD
ADD
% x 10
22nd Order harmonic
A9E
ABE
ADE
% x 10
23rd Order harmonic
A9F
ABF
ADF
% x 10
24th Order harmonic
AA0
AC0
AE0
% x 10
25th Order harmonic
AA1
AC1
AE1
% x 10
26th Order harmonic
AA2
AC2
AE2
% x 10
27th Order harmonic
AA3
AC3
AE3
% x 10
28th Order harmonic
AA4
AC4
AE4
% x 10
29th Order harmonic
AA5
AC5
AE4
% x 10
30th Order harmonic
AA6
AC6
AE6
% x 10
31st Order harmonic
AA7
AC7
AE7
% x 10
7�3�4�- DELETING PARAMETERS
The
Function
0x05
is implemented for these variables.
Table 70: Modbus memory map: Deleting parameters�
Parameters
Address
Valid data margin
Deleting energies
834
FF00
Deleting maximum and minimum values
838
FF00
Starting maximum demand
839
FF00
Deleting the hour counters (All tariffs)
83D
FF00
Deleting the maximum value of the maximum demand
83F
FF00
Deleting energies, maximum demand and maximum and minimum values
848
FF00
79
Instruction Manual
CVM-C11