PROGRAMMING THE ALARM RELAY 1
In this step, all the values corresponding to alarm relay 1 are programmed.
The variable code is selected on this screen, depending on
and
which will control
alarm relay 1.
Press key
for 3 seconds to edit the value. The
icon appears at the top of the screen.
To enter or modify the value, press the
key repeatedly, increasing the value of the flashing digit.
When the desired value is shown on the screen, move onto the next digit by pressing the key
to
modify the other values.
When you enter the code of a variable on the display, the symbols for that variable will be activated.
To validate the data, press
for 3 seconds and the
icon will disappear from the display.
Configuration values
Note:
Set the value to
000
if you do not wish to program a variable.
Table 43: Parameter codes used to program the outputs�
Parameter
Phase
Code
Phase
Code
Phase
Code
Phase
Code
Phase-Neutral Voltage
L1
01
L2
09
L3
17
-
-
Current
L1
02
L2
10
L3
18
-
-
Active power
L1
03
L2
11
L3
19
III
25
Inductive Reactive Power
L1
04
L2
12
L3
20
III
26
Capacitive Reactive Power
L1
05
L2
13
L3
21
III
27
Apparent power
L1
06
L2
14
L3
22
III
28
Power factor
L1
07
L2
15
L3
23
III
29
Cosine
φ
L1
08
L2
16
L3
24
III
30
% THD V
L1
36
L2
37
L3
38
-
-
% THD A
L1
39
L2
40
L3
41
-
-
Phase-Phase Voltage
L1/2
32
L2/3
33
L3/1
34
-
-
Frequency
-
31
-
-
-
-
-
-
Neutral current
-
35
-
-
-
-
-
-
Maximum current demand
L1
45
L2
46
L3
47
III
44
Active Power Maximum
Demand
-
-
-
-
-
-
III
42
56