9 SERVICE INTERVAL SUMMARY TABLE
:
Regular maintenance will keep the unit running at optimum performance. The values given in the table below are
provided for guidance only. They do not take into account individual factors that can lengthen or shorten the unit's
service life.
DEVICE
AT COMMISSIONING
2-3 MONTHS
12 MONTHS
Filters
-Replace
-Replace
Cooling coil
-Clean
-Check and clean the condensate drains
-Retighten the electrical connections
Electric heater
(option)
-Check the connections
-Clean
-Check the components
-Retighten the electrical connections
-Check the components
-Check the condensate drains
Humidifier (option)
*
-Check the connections
-Check the condition of
the tank; replace if
necessary
-Make sure that steam is evenly distributed
Fan(s)
- Check correct operation
-Retighten the electrical connections
-Retighten the electrical connections
Electrics box
-Check the connections
-Check the components
-Check the components
Hydraulic circuit
-Check the insulation
Water leak detection
sensor and relay
-Check correct operation
-Check correct
operation
-Check correct operation
Filter pressostat
-Check correct operation and
setpoint adjustment
-Check correct
operation and setpoint
adjustment
Check correct operation and setpoint
adjustment
Thermostat and fire
control relay
-Check correct operation
-Check correct
operation
-Check correct operation
Valve
-Check circuit for correct
operation and leaks
-Check correct operation
Pressure gauge
-Check the pressure and top up
or fill the circuit as necessary
* If a water softener or water treatment system is used, the water hardness should not be less than 40% of the initial
hardness and should never be less than 15°F.