GB-15
Maximum differential pressure allowable on hot water valve:
(1)
3-way valve
(2)
2-way valve
CW12 CW18
CW24
CW30
CW35
CW45
CW61
CW70
CW80
CW90
K
V
1
1
1.6
2.5
2.5
2.5
4
4
6.3
6.3
∆
P max
¹
[Kpa]
250
250
250 240 240 240 240 240 600 600
Valve
assembly
(standard
coil)
∆
P max
²
[Kpa]
1200
1200
1200 400 400 400 400 400 600 600
Hot water valve pressure drop
0.00
0.50
1.00
1.50
2.00
2.50
3.00
3.50
4.00
0.000
0.500
1.000
1.500
2.000
2.500
3.000
3.500
CW12
CW18
CW24
CW30
CW35
CW45
CW61
CW70
CW80
CW90
Pr
e
s
s
u
re
dr
op
(
m
WC)
Hydraulic output (m
3
/h)
Heating coil + valve pressure drop
0.00
1.00
2.00
3.00
4.00
5.00
6.00
7.00
8.00
0.000
0.500
1.000
1.500
2.000
2.500
3.000
3.500
CW12
CW18
CW24
CW30
CW35
CW45
CW61
CW70
CW80
CW90
Pr
e
s
s
u
re
dr
op
(
m
WC)
Water flow rate (m
3
/h)