GB-11
6-2 Cooling coil:
2 coil types have been predefined in order to provide the different water temperature ranges. Other types may be
selected for special water temperature ranges or specific performance levels.
Note: make sure that the chilled water supply pipes are insulated.
Moderately tighten the coil supply connections to avoid damaging the manifolds.
Coil specifications:
Flow rate and pressure drop for valve + coil:
CW
No. of
rows
12
18
24
30
35
45
61
70
80
90
115
4 rows
2.1 3.18 4.2 5.28 6.12 7.84 10.56
12.24
14.25
15.41
18.42
5 rows
1.79 2.70 3.57 4.49 5.10 6.66 8.97 10.20 12.04 13.05
Nominal water flow
rate* (m
3
/h)
6 rows
16.74
Valve K
v
4 6.3 6.3 10 10 16 16 25 25 25
40
4 rows
5.91 6.9 7.63 6.67 7.72 6.24 8.26 6.36 6.5 7.54
4.53
5 rows
5.73 6.29 6.96 6.18 7.06 6.22 7.33 6.11 6.07 7.06
P (Pa) Valve + Coil
(mWC)
6 rows
5.89
4 rows
2.79 2.58 4.51 2.83 3.79 2.43 4.41 2.43 3.29 3.85
2.15
5 rows
2.02 1.86 3.25 2.04 2.63 1.76 3.19 1.68 2.35 2.76
P (Pa) Valve alone
(mWC)
6 rows
1.77
* Return conditions: 24°C / 45% HR.
Water T°
∆
: 5°C
CW
12
18
24
30
35
45
61
70
80
90
115
Number of
coils
1 1 2 2 2 1 4 4 2 2 1
CW
Standard coil
(4 rows)
Capacity (l)
3.75 5.7 7.5 9.45 11.4 14 18.9 22.8 28 28 30.2
Number of
coils
1
1 2 2 2
1 4
4 2 2
CW
Coil
(5 rows)
Capacity (l)
4.5
6.8
8.7
11.3
13.6
16.8 22.6 27.2 33.6 33.6
Number of
coils
1
CW
Coil
(6 rows)
Capacity (l)
42.9
Number of
coils
CW
Special "S"
Coil
Capacity (l)
Refer to conditions for range