GB-14
Maximum differential pressure allowable on the cold-water valve:
(1) 3-way valve.
(2) 2-way valve
.
6-3 Heating coil and valve (option)
Moderately tighten the "coil supply" connections to avoid damaging the
manifolds
.
Coil specifications:
CW 12
CW 18
CW 24
CW 30
CW 35
CW 45
CW 61
CW 70
CW 80
CW 90
Number of
coils
1
1
1
1
1
1
2
2
2
2
Standard
coil
Capacity (l)
1.7
2.5
3.4
2.5
3.2
3.7
5
6.4
7.4
7.4
Pressure drop - heating coil*:
*Water T
∆
nominal flow rate: 20°C
CW12
CW18
CW24
CW30
CW35
CW45
CW61
CW70
CW80
CW90
CW115
K
V
4
6.3
6.3
10
10
16
16
25
25
25
40
∆
P max¹
[kPa]
240
600
600
600
600
500
500
400
400
400
1600
∆
P max ²
[kPa]
400
600
600
600
600
500
500
400
400
400
1600
CW 12
CW 18
CW 24
CW 30
CW 35
CW 45
CW 61
CW 70
CW 80
CW 90
Nominal water
flow rate* (m
3
/h)
0.42
0.61
0.84
0.93
1.15
1.43
1.87
2.3
2.72
2.91
Valve (
K
v
)
1
1
1.6
2.5
2.5
2.5
4
4
6.3
6.3
∆
P
coil +
valve (mWC)
3.69
4.71
4.97
3.85
4.76
7.45
4.64
5.97
5.66
6.45
∆
P
valve
(mWC)
1.92
0.98
2.2
2.44
2.62
4.14
2.44
2.62
3.77
4.28
EN
Summary of Contents for Magister 2 CW 12
Page 2: ......
Page 7: ...FR 5 3 2 CW 61 90 mod le eau glac e FR Montage UNDER 1 Montage OVER 3 et 5...
Page 31: ...FR 29 FR...
Page 60: ...GB 29...
Page 89: ...DE 29 DE...
Page 118: ...E 29...
Page 119: ......