EN - 23
CONDENSER configuration (continued)
Factory-set
parameters
[4-Machine
parameters]
menu
The
[4-Machine parameters]
menu contains the parameters used to configure
the machine. They were set in the factory and are locked. The symbol
appears at the top left of the screen.
In certain rare cases (such as adding the spray function) it may be necessary to
update a parameter. The parameters may be unlocked by changing parameter
A99. However, do not modify any parameters other than those that require
changing.
Parameter
No.
Parameter description
Display condition
A01
Unit type (flatbed or V-coil)
Number of coils (1)
Flatbed unit
A02
Parallel coil (no)
V-type unit
A03
Coil 1 type (1 refrigerant circuit, 2
refrigerant circuits)
A04
Coil circuit type (balanced or
unbalanced)
Flatbed unit & 2 refrigerant
circuits
A05
Coil 2 type (1 refrigerant circuit)
V-type unit
A07
Control type: On/Off (stages),
speed control or mixed
A08
Number of stages (1 to 6)
Control = On/Off or mixed
A09
Number of fan lines (1 or 2)
Flatbed unit & 2 refrig. circ.
A10
Spray (yes or no)
A30
Top of sensor range - circuit or
coil 1
A31
Bottom of sensor range - circuit or
coil 1
A32
Top of sensor range - circuit 2
2 refrigerant circuits
A33
Bottom of sensor range - circuit 2
2 refrigerant circuits
A34
Top of sensor range - coil 2
2 refrigerant circuits
A35
Bottom of sensor range - coil 2
2 refrigerant circuits
A99 Lock
parameters
(yes)