DRY COOLER configuration (continued)
Parameter
No.
Default values
Default
values
Display conditions
Setpoint 1
V-type or 1-coil unit/flatbed
unit
A121
Setpoint 1, coil 1
60°C
2 coils + flatbed unit
Setpoint 2
2 set V-type or 1-coil
unit/flatbed unit
A122
Setpoint 2, coil 1
50°C
2 set 2 coils/flatbed
unit
A125
Setpoint 1, coil 2
60°C
2 coils/flatbed unit
A126
Setpoint 2, coil 2
50°C
2 set 2 coils/flatbed
unit
Stage 1 hysteresis: 1 to 20°C
V-type or 1-coil unit/flatbed
unit
A150
Stage 1 hysteresis, coil 1: 1 to 20°C
5°C
2 coils/flatbed unit
Difference between stages 1 and 2:
1 to 5°C
Control = On/Off + No. of
stages
≥
2 + V-type or 1-coil
unit/flatbed unit
A151
Difference between stages 1 and 2 of
coil 1: 1 to 5°C
2°C
Control = On/Off + No. of
stages
≥
2 +2 coils/flatbed
unit
Hysteresis of stages 2, 3, 4, 5 or 6:
1 to 10°C
Delta of stages 2, 3, 4, 5 or 6: 1 to 5°C
Control = On/Off + based on
No. of V-type or
1-coil unit/flatbed unit
A152
to A160
Hysteresis of stages 2, 3, 4, 5 and 6 of
coil 1: 1 to 10°C
Delta of stages 2, 3, 4, 5 and 6 of coil 1: 1
to 5°C
5°C
Control = On/Off + based on
No. of 2 coils/flatbed
unit
A172
Stage 1 hysteresis, coil 2: 1 to 20°C
5°C
2 coils/flatbed unit
A173
Difference between stages 1 and 2 of
coil 2: 1 to 5°C
2°C
Control = On/Off + No. of
stages
≥
2 +2 coils/flatbed
unit
A174
to A182
Hysteresis of stages 2, 3, 4, 5 and 6 of
coil 2: 1 to 10°C
Delta of stages 2, 3, 4, 5 and 6 of coil 2:
1 to 5°C
Control = On/Off + based on
No. of 2 coils/flatbed
unit
A199
Outdoor spray temperature
35°C
Spray / elec. optimisation
Spray stage difference
Spray / water optimi
V-type or 1-coil unit/flatbed
unit
A200
Spray stage difference, coil 1
2°C
Spray / water optimi
2 coils/flatbed unit
A202
Spray stage difference, coil 2
2°C
Spray / water optimi
2 coils/flatbed unit
p
Turning on the unit: Power button