EN - 20
CONDENSER configuration
Configurations
Flatbed unit
V-type unit
Application
: condenser with one or two refrigerant circuits
Commissioning
and configuration
n
Turning on the unit:
The screen displays "machine off - on/off" in the
[2-Machine status]
menu.
Press ESC to go back to the menu list.
o
Main parameters to be set:
select the
[5-Settings parameters]
menu.
For information on navigating, go to the Control console / Navigation section.
Parameter
No.
Description
Default
values
Display conditions
Menu 5: Settings parameters
A100
Language
FR
A103
Control mode: local or remote
local
A104
Communication mode (baud)
9600 BMS
A105
Bus number
1 BMS
A110
Stage runtime balancing
yes
Control = On/Off (stages) or mixed
A113
Optimisation of water or electricity
consumption
Water
optimisation
Spray
A116
Link with CIAT chiller
yes
A120
No. of setpoints per circuit or coil
1
A121
Setpoint 1, circuit or coil 1
12 bar
A122
Setpoint 2, circuit or coil 1
12 bar
2 setpoints
A123
Setpoint 1, circuit 2
2 refrigerant ci flatbed unit
or
A125
Setpoint 1, coil 2
12 bar
V-type unit
A124
Setpoint 2, circuit 2
2 setpoints & 2 refrigerant circ. +
flatbed unit
or
A126
Setpoint 2, coil 2
12 bar
2 set V-type unit
Not av
ailable
fo
r CIAT c
h
illers
Circuit 1
Circuit 2
Line 1
Line 2
Coil 1
Coil 2
Line 1
Line 2
2 refrigerant circuits
Circuit 1
Circuit 2
1 refrigerant
circuit