EN - 26
BMS communication protocol (continued)
Fault memory
Counters
(read-only)
Register 200:
Fault 9 memory
Register 201:
Fault 8 memory
Register 202:
Fault 7 memory
Register 203:
Fault 6 memory
Register 204:
Fault 5 memory
Register 205:
Fault 4 memory
Register 206:
Fault 3 memory
Register 207:
Fault 2 memory
Register 208:
Fault 1 memory
0:
Fault memory empty
0x010: Fan fault, stage 1, line 1
0x011: Fan fault, stage 2, line 1
0x012: Fan fault, stage 3, line 1
0x013: Fan fault, stage 4, line 1
0x014: Fan fault, stage 5, line 1
0x015: Fan fault, stage 6, line 1
0x016: Fan fault, stage 1, line 2
0x017: Fan fault, stage 2, line 2
0x018: Fan fault, stage 3, line 2
0x019: Fan fault, stage 4, line 2
0x01A: Fan fault, stage 5, line 2
0x01B: Fan fault, stage 6, line 2
0x080: Temperature sensor fault, coil 1, circuit 1
0x081: Temperature sensor fault, coil 1, circuit 2
0x082: Temperature sensor fault, coil 2, circuit 1
0x083: Temperature sensor fault, coil 2, circuit 2
0x084: Temperature sensor fault, coil 1, circuit 1
0x085: Temperature sensor fault, coil 1, circuit 2
0x086: Temperature sensor fault, coil 2, circuit 1
0x087: Temperature sensor fault, coil 2, circuit 2
Registers 300 and 301:
Fan runtime, stage 1, line 1
Registers 302 and 303:
Fan runtime, stage 2, line 1
Registers 304 and 305:
Fan runtime, stage 3, line 1
Registers 306 and 307:
Fan runtime, stage 4, line 1
Registers 308 and 309:
Fan runtime, stage 5, line 1
Registers 310 and 311:
Fan runtime, stage 6, line 1
Registers 312 and 313:
Fan runtime, stage 1, line 2
Registers 314 and 315:
Fan runtime, stage 2, line 2
Registers 316 and 317:
Fan runtime, stage 3, line 2
Registers 318 and 319:
Fan runtime, stage 4, line 2
Registers 320 and 321:
Fan runtime, stage 5, line 2
Registers 322 and 323:
Fan runtime, stage 6, line 2
Register 324 to 398:
Reserved