37
Trouble
Shooting
12-3-B. PRODUCT IS NOT LEVEL
Symptom
1. Cold water is working properly, but there is no Ice.
2. Connect Test Board: LED22 starts blinking.
Cause of Defect
Due to product not being level, over-freezing and/or irregular Ice will be created.
AS Procedure
Adjust the legs to level the unit.
Level is provided in the drip pan. To remove level, use a sharp object to pop out. Must be
place on top of the unit towards the front.
How to Diagnose
Press the Ice button to dispense Ice.
There is Ice, but Ice shape is irregular.
- Remove Front-upper cover and disassemble the dispense
tunnel to check the shape of Ice.
1
2
Two Ice frozen together
Ice is lopsided
Product positioning is not
level, thus causing over- freez-
ing and/or Ice irregularity.