Installation
3-13
Command
Description
SOURce:POWer?
Query power setting value.
SOURce:VOLTage:CUTOFF Set the cutoff voltage parameters. Unit (V). There are three
decimal points. Range based on machine specifications.
SOURce:VOLTage:CUTOFF? Query cutoff voltage setting value.
SOURce:CURRent:CUTOFF Set the cutoff current parameters. Unit (A). There are three
decimal points. Range based on machine specifications.
SOURce:CURRent:CUTOFF? Query cutoff current setting value.
SOURce:CURRent:SLEW
Set the current slew rate parameters. Unit (A/ms). There are
three decimal points. Range based on machine
specifications.
SOURce:CURRent:SLEW?
Query current slew rate setting value.
SOURce:MODe
Set output mode.
SOURce:MODe?
Query output mode.
MEASure:ALL?
Query all measurement values.
MEASure:OPER?
Query operation status.
MEASure:TIME?
Query measurement time.
MEASure:STATe?
Query protection status.
MEASure:TEMP?
Query measurement temperature.
MEASure:VOLT?
Query measurement voltage.
MEASure:CURR?
Query measurement current.
MEASure:POW?
Query measurement power.
MEASure:AH?
Query measurement AH.
MEASure:KWH?
Query measurement KWH.
MEASure:DCIR?
Query measurement DCIR.
BATTery:SPEC:ALL?
Query battery simulator specifications.
BATTery:ALL
Set battery simulator all parameter values.
BATTery:ALL?
Query battery simulator all the setting parameter values.
BATTery:OUTPut
Set battery simulator output status.
(0~2/OFF/PAUSE/CONTINUE)
BATTery:OUTPut?
Query battery simulator output status.
(OFF LINE/OFF/ON/PAUSE/PROGRAM)
BATTery:INITial
Set the battery simulator initial mode parameters. (0/Initial
CAP, 1/Initial VOL)
BATTery:INITial?
Query battery simulator initial mode setting value.
BATTery:PARAmeter
Set the battery simulator parameter to Ah or SOC.
BATTery:PARAmeter?
Query battery simulator parameter to be Ah or SOC.
BATTery:INITial:CAP
Set the battery simulator initial CAP parameters. Unit: %.
BATTery:INITial:CAP?
Query battery simulator initial CAP setting value.
BATTery:INITial:VOLT
Set the battery simulator initial VOL parameters. Unit: %.
BATTery:INITial:VOLT?
Query battery simulator initial VOL setting value.
BATTery:CAP
Set the battery simulator CAP parameters. (float) Battery
pack total capacity; unit: Ah.
BATTery:CAP?
Query battery simulator CAP setting value.
BATTery:OCP
Set the battery simulator OCP parameters. (float)
BATTery:OCP?
Query battery simulator OCP setting value.
BATTery:ESR
Set the battery simulator ESR parameters. (float) The range
is
1mΩ
~
1000mΩ
.
BATTery:ESR?
Query battery simulator ESR setting value.
Summary of Contents for 69200-1
Page 1: ......
Page 2: ......
Page 3: ...Charge Discharge Controller 69200 1 User s Manual Version 1 3 April 2017...
Page 8: ...vi...
Page 12: ......
Page 14: ......
Page 20: ......
Page 70: ......
Page 78: ......
Page 80: ...Charge Discharge Controller 69200 1 User s Manual 5 2 please notify Chroma for calibration...
Page 82: ......
Page 84: ......