Chapter 5 Function Parameter Detail SVF-MN Series Frequency Inverter Operation Manual
85
600.0s
P13 2nd Deceleration time
0.1
~
6000.0s or 0.01
~
600.0s
10.0
Acc. Time is the time that the output freq. of the drive needs from
0Hz to max operation freq. (P03).
Dec. time is the time that the output freq. of the drive needs from
max operation freq. (P03) to 0Hz.
If using 2nd Acc. And Dec. time, one terminal from S2~S5 need to
be selected, and set it to selection Acc. And Dec. time 2. If this
terminal is on, then select 2nd Acc. time and Dec. time, if off, then
select 1st Acc. and Dec. time.
P14
Digital frequency settings
0.00
~
P03
0.00
When keyboard digital settings (P00=0) is selected as frequency
source, this function code value is regarded as the initial value of
drive digital given frequency.
P15
Jog Acc. and
Dec. time
0.1
~
600.0s or 0.01
~
600.00s
10.0
P16
Job run
frequency
0.00Hz
~
P03 6.00
Jog run time refer to the time that the drive needed from 0Hz to max
output frequency or from max output frequency to 0Hz.
P17
1st stage freq. settings 0.00 Hz
~
P03 0.00