Chapter 5 Function Parameter Detail SVF-MN Series Frequency Inverter Operation Manual
133
0
:
Retain
1
:
Modbus
This parameter is used to select communication protocol format.
P158 Current sensor fault valid
0
~
1 1
0
:
Invalid
1
:
Valid
P159 PWM
mode
0
~
1 0
0
:
PWM mode 0
The energy dissipation could be decreased if carrier frequency is
self-adapted.
1
:
PWM mode 1
The frequency inverter heat would increase slightly if carrier
frequency is fixed.
P160 Zero-frequency corresponding
keyboard potentiometer voltage
0.0
~
10.0V
0.5
P161
Max freq. corresponding
keyboard potentiometer input
voltage
0.0
~
10.0V 9.5
It is used to set the relation between keyboard potentiometer input
voltage scope and corresponding set frequency scope.
P162
Reverse keyboard potentiometer selection
0
~
1 0
0
:
No reverse
1
:
Reverse
This parameter is set by reverse parameter P160 and P161, when